Wiring inputs and outputs
Wiring specifications
Input wiring
Input
Thermistor
Dry contact
0–5 Vdc
0–10 Vdc
Pulse counter
TLO
Output wiring
To size output wiring, consider the following:
•
Total loop distance from the controller to the controlled device
NOTE Include the total distance of actual wire. For 2-conductor wires, this is twice the cable length.
•
Acceptable voltage drop in the wire from the controller to the controlled device
•
Resistance (Ohms) of the chosen wire gauge
•
Maximum current (Amps) the controlled device requires to operate
TruVu™ VAVB3-E2
Installation and Start-up Guide
Maximum length
1000 feet
(305 meters)
1000 feet
(305 meters)
1000 feet
(305 meters)
26
Minimum gauge
22 AWG
26 AWG
22 AWG
CARRIER CORPORATION ©2022
Shielding
Shielded
Shielded
Shielded