To Wire The Co2 Sensor To The Controller - Carrier TruVu VAVB3-E2 Installation And Startup Manual

Table of Contents

Advertisement

Wiring sensors to the TV-VAVB3-E2's inputs

To wire the CO2 sensor to the controller

Part #33ZCSPTCO2LCD-01 (Display model)
Part #33ZCSPTCO2-01 (No display)
Part #33ZCT55CO2 (No display)
A CO
sensor monitors carbon dioxide levels. As CO
2
source. These sensors also monitor temperature using a 10K thermistor.
A CO
sensor can be wall-mounted or mounted in a return air duct. (Duct installation requires an Aspirator Box
2
Accessory - Part #33ZCASPCO2.)
The sensor has a range of 0–2000 ppm and a linear 4-20 mA output. This is converted to 1-5 Vdc by a 250 Ohm,
1/4 watt, 2% tolerance resistor connected across the zone controller's CO
NOTE Do not use a relative humidity sensor and CO
#33ZCSPTCO2
Wire the sensor to the controller. See appropriate diagram below.
1
Verify the J7 jumper on the sensor is set to 0-5 Vdc.
2
Wiring diagram for #33ZCSPTCO2:
#33ZCT55CO2
Wire the sensor to the controller. See appropriate diagram below.
1
Install a field supplied 250 Ohm 1/4 watt 2% tolerance resistor across the controller's IN-01 and Gnd
2
terminals.
TruVu™ VAVB3-E2
Installation and Start-up Guide
levels increase in a linked system, IAQ is provided to the air
2
input terminals.
2
sensor on the same zone controller.
2
36
CARRIER CORPORATION ©2022