Wiring specifications

Input wiring
Input
Thermistor
Dry contact
0–5 Vdc
0–10 Vdc
Pulse counter
TLO
Output wiring
To size output wiring, consider the following:
Total loop distance from the controller to the controlled device
NOTE Include the total distance of actual wire. For 2-conductor wires, this is twice the cable length.
Acceptable voltage drop in the wire from the controller to the controlled device
Resistance (Ohms) of the chosen wire gauge
Maximum current (Amps) the controlled device requires to operate

To wire inputs and outputs

WARNING Do not apply line voltage (mains voltage) to the controller's ports and terminals.
The Gnd terminal is shared by the inputs/outputs to the top and bottom of it.
TruVu™ VVTBP-E2
Installation and Start-up Guide
Maximum length
1000 feet
(305 meters)
1000 feet
(305 meters)
1000 feet
(305 meters)
25
Minimum gauge
22 AWG
26 AWG
22 AWG
Wiring inputs and outputs
Shielding
Shielded
Shielded
Shielded