Alarms - Carrier TruVu VAVB3-E2 Installation And Startup Manual

Table of Contents

Advertisement

Appendix A: TV-VAVB3-E2 Points/Properties

Alarms

Navigation:
i-Vu® / Field Assistant:
Point Name/Description
Space Temperature – Indicates if the space temperature sensor exceeds the high or
low alarm limit.
Alarming Temperature – Indicates the space temperature value that caused the space
temperature alarm. This value is only displayed when the Space Temperature alarm
(above) is in Alarm.
Alarm Limit Exceeded – Indicates the value of the space temperature alarm limit that
caused the space temperature alarm condition. Value is only displayed when the Space
Temperature alarm (above) is in Alarm.
Space Temp Sensor – Indicates if the space temperature sensor fails.
Wireless Battery Strength Alarm – Indicates one of the configured wireless space
temperature sensors is displaying low charge strength.
Wireless Signal Strength Alarm – Indicates one of the configured wireless space
temperature sensors is displaying low radio signal strength.
ZS/WS Sensor Configuration – Indicates if the ZS or wireless space temperature
sensor is not configured correctly.
Indoor Air Quality – Indicates if the occupied CO
Alarm Limit.
Supply Air Temperature – Indicates if the supply air temperature exceeds the high
temperature alarm limit or drops below the low temperature alarm limit.
Filter – Indicates if the filter's runtime hours exceeds the runtime alarm limit.
Space Relative Humidity – Indicates if the relative humidity exceeds the high RH alarm
limit.
Network OAT - Indicates if the controller is not receiving a valid OAT value over the
network.
Airside Linkage Status – If the controller is the VVT Master, Alarm indicates that it lost
Linkage communications with the air source. If the controller is a slave, Alarm indicates
that it lost Linkage communications with the VVT master.
Smart HWV 1 Alarm – Indicates if the Smart Valve fails.
Heat Valve Cycling – Indicates if the heating valve exceeds the limit of cycles per
period.
Heat Valve Fail – Indicates if the heating valve fails.
TruVu™ VAVB3-E2
Installation and Start-up Guide
Properties
Control Program
>
level exceeds the Occupied High CO2
2
132
Alarms
>
Range
R:
Normal/Alarm
R:
-56 to 245°F
(-48.9 to 118.3°C)
R:
-56 to 245°F
(-48.9 to 118.3°C)
R:
Normal/Alarm
R:
Normal/Alarm
R:
Normal/Alarm
R:
Normal/Alarm
R:
Normal/Alarm
R:
Normal/Alarm
R:
Clean/Dirty
R:
Normal/Alarm
R:
Normal/Alarm
R:
Normal/Alarm
R:
Normal/Alarm
R:
Normal/Alarm
R:
Normal/Alarm
CARRIER CORPORATION ©2022
All rights reserved