Wiring for communications

The Zone Ctrl II communicates using BACnet on the following types of network segments:
MS/TP communicating at 9600 bps, 19.2 kbps, 38.4 kbps, or 76.8 kbps
ARC156 communicating at 156 kbps
NOTE For more networking details, see the Open Controller Network Wiring Installation Guide.

Wiring specifications for BACnet MS/TP and ARC156

Cable:
Maximum length:
WARNING Do not apply line voltage (mains voltage) to the controller's ports and terminals.

To wire the controller to the BACnet network

WARNING Attaching any ARCNET or MS/TP network to the Act Net port damages BT485s, DIAG485s, or
terminating resistors on that network.
1
Pull the screw terminal connector from the controller's power terminals labeled Gnd and 24 Vac.
2
Check the communications wiring for shorts and grounds.
3
Connect the communications wiring to the controller's screw terminals labeled Net +, Net -, and Shield.
NOTE Use the same polarity throughout the network segment.
4
Set the communication type and baud rate.
For...
ARC156
MS/TP
NOTE Use the same baud rate for all controllers on the network segment.
Zone Ctrl II and
VAV Zone II Secondary Duct Installation and Start-up Guide
Error! No text of specified style in document.
22 AWG or 24 AWG, low-capacitance, twisted, stranded, shielded copper wire
2000 feet (610 meters)
Set BACnet ARC156 or
MS/TP
jumper to...
ARC156
MS/TP
Set DIP switches 1 and 2 to...
N/A. Baud rate will be 156 kbps regardless of
the DIP switch settings.
The appropriate baud rate. See the MS/TP
Baud diagram on the controller.
15
Installing the Zone Ctrl II
CARRIER CORPORATION ©2019
All rights reserved