Wiring for communications

The MPC Open XP communicates using BACnet on the following types of network segments:
MS/TP communicating at 9600 bps, 19.2 kbps, 38.4 kbps, or 76.8 kbps
ARC156 communicating at 156 kbps
NOTE For more networking details, see the Open Controller Network Wiring Installation Guide.

Wiring specifications for BACnet MS/TP and ARC156

Cable:
Maximum length:
WARNING Do not apply line voltage (mains voltage) to the controller's ports and terminals.

To wire the controller to the network

1
Pull the screw terminal connector from the controller's power terminals labeled 24 Vac/26 Vdc and Return
(Ground).
2
Check the communications wiring for shorts and grounds.
3
Connect the communications wiring to the controller's screw terminals labeled Net +, Net -, and Shield.
NOTE Use the same polarity throughout the network segment.
4
Set the communication type and baud rate.
For...
MS/TP
ARC156
NOTE Use the same baud rate for all controllers on the network segment.
5
Wire the controllers on a BACnet MS/TP or BACnet ARC156 network segment in a daisy-chain configuration.
6
Install a BT485 on the first and last controller on a network segment to add bias and prevent signal
distortions due to echoing.
MPC Open XP
MPC Open XP IO48/816
Installation and Start-up Guide
22 AWG or 24 AWG, low-capacitance, twisted, stranded, shielded copper wire
2000 feet (610 meters)
Set BACnet Mode jumper to...
BACnet MS/TP
BACnet ARC156
Carrier Proprietary and Confidential
Set DIP switches 7 and 8 to...
The appropriate baud rate. See the BACnet MS/TP
Baud diagram on the controller.
N/A. Baud rate will be 156 kbps regardless of the DIP
switch settings.
9
Installing the MPC Open XP
CARRIER CORPORATION ©2017
All rights reserved