Appendix A: TV-VAVB3-E2 Points/Properties
Point Name/Description
Act Net Vlv 1 Max Pos – The maximum position that the Act Net valve will control to.
T55 Override Duration – The amount of time that the controller runs in the occupied
mode when a user presses the T55 sensor's override button for 1 to 10 seconds.
Pushbutton Override must be set to Enable.
Environmental Index Enable – If enabled, when a zone is occupied, it monitors the
deviation of space temperature from effective heating and cooling setpoint range. It
monitors optional relative humidity if RH Control is set to Enable and/or monitors CO
DCV Control is set to Enable.
Local Sensor Calibration
Space Temperature – The current space temperature.
Space Temp Calibration – A calibration offset value to allow the local space
temperature sensor to be adjusted to match a calibrated standard measuring the
temperature in the same location.
Supply Air Temperature – Displays the current supply air temperature.
Supply Air Temp Calibration – A calibration offset value to allow the supply air
temperature sensor to be adjusted to match a calibrated standard measuring the
temperature in the same location.
Space Relative Humidity – Displays the current value of relative humidity sensor, if
present.
Relative Humidity Calibration – You can enter a calibration offset for the relative
humidity. The offset is added to or subtracted from the controller's RH input value, and
the calculated value is shown in the Status > Space Relative Humidity.
TruVu™ VAVB3-E2
Installation and Start-up Guide
2
110
Default/Range
D:
100%
R:
0 to 100%
D:
1 hr
R:
1 to 4 hr
D:
Enable
R:
Disable/Enable
if
R:
-56 to 245°F
(-48.9 to 118.3°C)
D:
0 °F/ °C
R:
-9.9 to 10 °F
(-5.5 to 5.5 °C)
R:
-56 to 245°F
(-48.9 to 118.3°C)
D:
0 °F/ °C
R:
-9.9 to 10 °F
(-5.5 to 5.5 °C)
R:
100%0 to 100%
D:
0%
R:
-15 to 15%rh