Appendix D: Bacnet Points List - Carrier TruVu VAVB3-E2 Installation And Startup Manual

Table of Contents

Advertisement

Appendix D: BACnet points list

Appendix D: BACnet points list
Point Name
Occupied Cooling Setpoint
Occupied Heating Setpoint
Unoccupied Cooling Setpoint
Unoccupied Heating Setpoint
Occupancy Contact State
Air Source Outdoor Air Temp
Air Source Static Pressure
Air Source Supply Air Temp
Baseboard Heating Capacity
Cooling Demand Level
Damper Position
Effective Cool Setpoint
Effective Heat Setpoint
Fan Off Delay
Filter Runtime
Filter Service Alarm Timer
Heating Capacity
Heating Demand Level
Heating Lockout Temperature
Indoor Air Quality CO2 (ppm)
lux sensor BACnet accessible
Occ Override Delay
Occupied RH Control Setpoint
Outdoor Air Temperature
Override Time Remaining
Power Fail Restart Delay
Setpoint Adjustment
Setpoint Adjustment Range
Space Relative Humidity
Space Temperature - Prime Variable
TruVu™ VAVB3-E2
Installation and Start-up Guide
Point
Units
Access
R/W
°F
R/W
°F
R/W
°F
R/W
°F
R
0=Open
1=Closed
R
°F
R
in H2O
R
°F
R
%
R
R
%
R
°F
R
°F
R/W
sec
R
hr
R/W
hr
R
%
R
R/W
°F
R
ppm
R
R/W
min
R/W
%rh
R
°F
R
min
R/W
sec
R
°F
R/W
°^F
R
%rh
R
°F
142
Default
BACnet Point Name
Value
75
occ_cl_stpt
70
occ_ht_stpt
90
unocc_cl_stpt
60
unocc_ht_stpt
occ_switch
link_ahu_oat
link_ahu_static
link_sat
bas_bd_ht_cap
cool_demand_level
dpr_pos
eff_cl_stpt
eff_ht_stpt
120
fan_delay_off
filter_rntm
0
filter_service_hrs
htg_cap
heat_demand_level
70
oat_ht_lockout
iaq
lux_bn
15
occ_ovr_delay
65
occ_dehum_stpt
oa_temp
ovrde_time
60
start_delay
stpt_adj
2
stpt_adj_range
space_rh
space_temp
CARRIER CORPORATION ©2022
BACnet
BACnet Object
ID
AV:3001
AV:3002
AV:3003
AV:3004
BI:1001
AV:2609
AV:2610
AV:2608
AV:2031
AV:9006
AV:1013
AV:3005
AV:3006
AV:9024
AV:2015
AV:2019
AV:2030
AV:9036
AV:9003
AV:1009
AV:9028
AV:3011
AV:1003
AV:2016
AV:9007
AV:1006
AV:9015
AV:1011
AV:2007