Carrier TruVu VAVB3-E2 Installation And Startup Manual page 99

Table of Contents

Advertisement

Local Devices table
Blue dot
Blink
NOTE If a device's IP address is the loopback address (127.0.0.1), it is considered unconfigured and unlocked.
The IP address, subnet mask, and default gateway fields are blank in the Ports and Local Network tabs. You can
configure it in the Local Devices table.
TruVu™ VAVB3-E2
Installation and Start-up Guide
A blue dot appears for the most recent device to have the:
Blink button clicked in the table
Address or Location entered
DSC button pressed on the device
NOTE If the device is not already listed in the table, pressing the DSC
button immediately adds it to the table and displays a blue dot.
TIP You can build a table of devices in the order that you've pressed the
DSC buttons. Clear the table and then press each DSC button in turn. The
devices will be listed in the table in the order in which the button was pressed,
but only the most recent one will show the blue dot.
Click the Blink button to prompt the Locator LED to flash for 15 seconds,
allowing you to verify the controller's physical location. After flashing, whenever
the actuator moves, the LED rotates in the same direction. LED rotation is
automatically disabled after 1 hour and can be re-enabled by pressing the Blink
button again.
NOTES
The blue dot appears when you Blink a device.
You can Blink a locked device.
93
To set up the controller through the Comm/Service ports
CARRIER CORPORATION ©2022
All rights reserved