Carrier TruVu VAVB3-E2 Installation And Startup Manual page 149

Table of Contents

Advertisement

Point Name
Standby Offset
Supply Air Temperature
System Outdoor Air Temperature
System Setpoint Adjustment
System Space AQ
System Space RH
System Space Temperature
Airside Linkage Status
Fan
Heat Enable
Occupancy Status
Reset Filter Alarm
Setpoint Adjustment
Shutdown
VAV Reheat
Air Source Mode
BAS On / Off
Optimal Start Type
Space Temp Source
Terminal Mode
TruVu™ VAVB3-E2
Installation and Start-up Guide
Point
Units
Access
R/W
°F
R
°F
R/W
°F
R/W
°F
R/W
ppm
R/W
%
R/W
°F
R
0=Not Active
1=Active
R
0=Off
1=On
R/W
0=Disable
1=Enable
R
0=Unoccupied
1=Occupied
R/W
0=Off
1=On
R/W
0=Disable
1=Enable
R/W
0=Inactive
1=Active
R/W
0=Disable
1=Enable
R
1=OFF
2=WARM-UP
3=HEAT
4=COOL
5=FREECOOL
6=PRESSURIZE
7=EVACUATE
8=VENT
R/W
1=Inactive
2=Occupied
3=Unoccupied
R/W
1=None
2=Temp Compensated
3=Learning Adaptive
R
1=Sensor Failure
2=SPT Sensor
3=T55 / T56
4=Network
5=Airside Linkage
6=Locked Value
7=ZS Sensor
8=Wireless Sensor
R
1=Off
2=Heating
3=Warm-Up
4=Vent
5=N/A
6=Cooling
143
Appendix D: BACnet points list
Default
BACnet Point Name
Value
0
stdby_offset
sa_temp
-999
system_oat
-999
system_stpt_adj
-999
system_iaq
-999
system_rh
-999
system_spt
a_link_status
sfan_status
Active (1)
ht_enable
occ_status
Inactive (0)
filter_rntm_clr
Active (1)
stpt_adj_enable
Active (1)
shutdown
Active (1)
vav_reheat
link_ahu_mode
1
keypad_ovrde
2
start_type
spt_status
terminal_status
CARRIER CORPORATION ©2022
BACnet
BACnet Object
ID
AV:1017
AV:1008
AV:1901
AV:1913
AV:1903
AV:1904
AV:1902
BV:2601
BV:1003
BV:1012
BV:2008
BV:7517
BV:1013
BV:9001
BV:1029
MSV:2005
MSV:1001
MSV:2009
MSV:2003
MSV:2006
All rights reserved