Wiring specifications

For...
Use...
BACnet/IP
CAT5e or higher Ethernet cable
Ethernet
MS/TP*
22 AWG, low-capacitance, twisted, stranded,
shielded copper wire *
ARCNET*
*
For details see the Open Controller Network Wiring Guide.
WARNING Do not apply line voltage (mains voltage) to the controller's ports and terminals.

To connect the TV-MPCXP1628-NR to the Ethernet

Connect an Ethernet cable to the Gig-E Ethernet port.
NOTE Be careful NOT to plug your cable into the Service Port.
NOTE If your system has controllers on different IP subnets separated by an IP router, you must configure one
controller on each subnet as a BACnet Broadcast Management Device (BBMD). Do not configure more than one
BBMD per subnet as this may cause circular routes. See To set up BACnet Broadcast Management Devices
(BBMDs) (page 22).
TruVu™ MPC Controller (part no. TV-MPCXP1628-NR)
Installation and Start-up Guide
Maximum Length
328 feet (100 meters)
2000 feet (610 meters)