EXAMPLE If the controller's address is 25, point the arrow on the Tens (10's) switch to 2 and the arrow
on the Ones (1's) switch to 5.
0
0
Turn on the UC Open XP's power switch. The controller reads the address each time you apply power to it.
3
NOTE The factory default setting is "00" and must be changed to successfully install your UC Open XP.

Wiring the UC Open XP to the MS/TP network

The UC Open XP communicates using BACnet on an MS/TP network segment communications at 9600 bps,
19.2 kbps, 38.4 kbps, or 76.8 kbps.
Wire the controllers on an MS/TP network segment in a daisy-chain configuration.
Install a BT485 on the first and last controller on a network segment to add bias and prevent signal
distortions due to echoing.
See the MS/TP Networking and Wiring Installation Guide for more details.

Wiring specifications

Cable:
Maximum length:
UC Open XP/UC Open XP IO
10's
1's
22 AWG or 24 AWG, low-capacitance, twisted, stranded, shielded copper wire
2000 feet (610 meters)
11