Appendix A: TV-VAVB3-E2 Points/Properties

NOTE Engineering units shown in this document in the defaults and ranges are strictly for reference. You must
enter an integer only.

Status

Navigation:
i-Vu® / Field Assistant:
Point Name/Description
Terminal Mode – The controller's current operating status.
Terminal Type – The type of zone terminal that the controller is installed on.
Space Temperature - Prime Variable – The space temperature value currently used for
control.
Primary Airflow – The current airflow measured through the primary air damper.
Damper Position – The current damper position.
Supply Air Temperature – Displays the current supply air temperature.
Heating Capacity – The current reheat capacity when the zone is configured for reheat.
Baseboard Heating Capacity – The current baseboard heat capacity when the zone is
configured for Combination Baseboard or Non-ducted Heat.
Outdoor Air Temperature – The current outdoor air temperature from a linked air
source, if available, or from another network source.
TruVu™ VAVB3-E2
Installation and Start-up Guide
Properties
Control Program
>
107
Appendix A: TV-VAVB3-E2 Points/Properties
Status
>
Range
R:
Off
Heating
Warm-up
Vent
Cooling
Dehumidify
Reheat
Pressurize
Evacuate
Shutdown
IAQ Override
Air Balancing
R:
Single Duct
Parallel Fan
Series Fan
R:
-56 to 245°F
(-48.9 to 118.3°C)
R:
0 to 99999 cfm
(liters/second)
R:
0 to 100%
R:
-56 to 245°F
(-48.9 to 118.3°C)
R:
0 to 100%
R:
0 to 100%
R:
-56 to 245°F
(-48.9 to 118.3°C)
CARRIER CORPORATION ©2022