Appendix A: TV-VAVB3-E2 Points/Properties
Occupancy Contact State - Current hardware state of the controller's IN-04 input.
Sensor Invalid – This internal input monitors the communication between the controller
and the SPT sensor. Off indicates communication is normal.
Rnet Sensed Occupancy – Displays occupancy status detected by wireless infrared
motion sensor.
Hot Water Valve - The current value of the controller's AO-01 output.
Hot Wtr Vlv 1 – The current value of the controller's output to the Smart Valve.
Heating Stage 1 - The current hardware state of the controller's BO-01 output.
Heating Stage 2 - The current hardware state of the controller's BO-02 output.
Fan S/S or EH 3 - The current hardware state of the controller's BO-03 output. The
function of this output depends on the terminal type.
TruVu™ VAVB3-E2
Installation and Start-up Guide
138
R:
Open/Closed
R:
Off/On
R:
Off/On
R:
0 to 100%
R:
0 to 100%
R:
Off/On
R:
Off/On
R:
Off/On