4 Maintenance

4.4.5 Function test of Automatic Stop

4.4.5 Function test of Automatic Stop
Performing the function test
1
2
114
Action
Start the robot system and change the op-
erating mode to auto mode.
Activate the Automatic Stop, for example
by opening the connected robot cell door,
which has interlock connection with Auto-
matic Stop.
© Copyright 2019-2022 ABB. All rights reserved.
Note
The test is passed if the event message
90523 Safety Controller Protective Stop
triggered appears in the event log.
If the event message 90523 Safety Control-
ler Protective Stop triggered does not ap-
pear in the event log, then the test has
failed and the root cause of the failure must
be found.
Product manual - OmniCore E10
3HAC079399-001 Revision: C