DISPLAY POINT
DISPLAY POINT
DISPLAY POINT
DISPLAY POINT
DISPLAY POINT
DISPLAY POINT operations display addressable device status on the LCD display. After the
status of the device is displayed, the UP key may be used to display the status of the next highest
addressable device, and the DOWN key to display the status of the previous addressable device.
The sequence of point display is Detector points 01-99, Module points 01-99, NAC bell circuits 01-
02, System parameters, and Zones 1-56.
A typical Read Status display is as follows:
NORMAL
NORMAL
NORMAL
NORMAL is the present status (could be ALARM, TRBL_#, DISABL, etc.)
NORMAL
SMOKE(DET) is the device type, P P P P P indicates that this is a Photoelectric detector (could be I I I I I if
SMOKE(DET)
SMOKE(DET)
SMOKE(DET)
SMOKE(DET)
Ionization, PULL BOX, HORN CKT, etc.), and 01
WEST HALLWAY
WEST HALLWAY
WEST HALLWAY
WEST HALLWAY
WEST HALLWAY is the custom label programmed for this device.
Z56
Z56
Z56
Z56 is the assigned software zone.
Z56
If the point is not installed, a Read Status command to that point will result in a NOT INSTALLED
message on the display.
READ HISTORY:
READ HISTORY:
READ HISTORY:
READ HISTORY:
READ HISTORY:
The MS-9200 has a 500-event history buffer. Stored events include Point Status, System
Troubles, and ACKNOWLEDGE/STEP, ALARM SILENCE, DRILL and SYSTEM RESET key
presses. All events are recorded with the time and date. History events are stored in volatile
memory, therefore, removal of primary AC power and secondary battery power will clear the
history buffer. To clear the History file without removing power, see Section 3.3.02. To view
events in the history file, use the Up and Down arrow keys to step through the events.
PRINT PROGRAM:
PRINT PROGRAM:
PRINT PROGRAM:
PRINT PROGRAM:
PRINT PROGRAM:
All user programmed options including device types, software zone assignments and system
parameters may be printed. The printout also includes current system status. See Section 2.16
for instructions on connecting a printer.
PRINT HISTORY:
PRINT HISTORY:
PRINT HISTORY:
PRINT HISTORY:
PRINT HISTORY:
The entire 500-event history file may be printed using the PRINT HISTORY feature. Refer to
Section 2.16 for instructions on connecting a printer.
Technical Manuals Online! - http://www.tech-man.com
NORMAL SMOKE DET P01
WEST HALLWAY
01 is the device address.
01
01
01
Document # 50428
Rev. B1
7/28/97
firealarmresources.com
Z56
NOT INSTALLED
NOT INSTALLED
NOT INSTALLED
NOT INSTALLED
P/N 50428:B1
71