Wiring The Signaling Line Circuit - Fire-Lite Alarms MS-9200 Technical Manual

Addressable fire control panel (export version)
Table of Contents

Advertisement

2.7
2.7 Wir
2.7
2.7
2.7
Wir
Wir

Wiring the Signaling Line Circuit

Wir
ing the Signaling Line Circuit
ing the Signaling Line Circuit
ing the Signaling Line Circuit
ing the Signaling Line Circuit
The MS-9200 communicates with addressable initiating, monitor and control devices through a Signaling
Line Circuit (SLC) Loop. This SLC loop can be wired to meet the requirements of NFPA Style 4 (see
Figure 2.7), Style 6 (see Figure 2.8) or Style 7 (see Figure 2.9). Surge protection for the SLC Loop may be
provided by using one of the compatible surge suppressors listed in Table G-1 of the Appendix. The SLC
Loop is allowed to leave the building only with use of an approved surge suppressor (refer to Table G-1).
Be certain to change the decade wheels on all detectors and modules from the factory '00' settings.
ISOLATOR MODULES
ISOLATOR MODULES
ISOLATOR MODULES
ISOLATOR MODULES
ISOLATOR MODULES
Isolator Modules permit a zone of detectors and modules to be electrically 'isolated' from the remainder of
the Communications Loop, allowing critical loop components to function in the event of a short circuit on
the SLC Loop wiring (see Figures 2.7, 2.8 and 2.9). These are required to meet the requirements of NFPA
Style 7.
MONITOR MODULES
MONITOR MODULES
MONITOR MODULES
MONITOR MODULES
MONITOR MODULES
Addressable Monitor Modules allow the control panel to monitor entire circuits of conventional normally-
open contacts, alarm initiating devices, manual pull stations, 4-wire smoke detectors, heat detectors,
waterflow, supervisory devices (see Figures 2.14 and 2.15) and conventional detectors (see Figures 2.16
and 2.17). The BG-10LX is an addressable manual pull station which contains a miniature monitor module
providing point annunciation (see Figures 2.7, 2.8 and 2.21).
CONTROL MODULES
CONTROL MODULES
CONTROL MODULES
CONTROL MODULES
CONTROL MODULES
Through addressable Control Modules, the control panel can selectively activate Notification Appliance
Circuits or Form-C output relays (see Figures 2.18 through 2.20).
ADDRESSABLE DETECTORS
ADDRESSABLE DETECTORS
ADDRESSABLE DETECTORS
ADDRESSABLE DETECTORS
ADDRESSABLE DETECTORS
Through the Communications Loop, the MS-9200 communicates with addressable ionization, photoelectric,
and photoelectric/thermal detectors (see Figure 2.22).
DEVICE CAPACITY
DEVICE CAPACITY
DEVICE CAPACITY
DEVICE CAPACITY
DEVICE CAPACITY
The capacity of each MS-9200 includes up to 99 addressable detectors, and an additional combination of
up to 99 addressable pull stations, control modules and monitor modules. In addition, the panel supports 2
Notification Appliance (Bell) Circuits.
Note: Refer to Appendix A and the installation drawings supplied with each loop device for rating and
specification information.
Table 2.1: Communications Loop Performance
Table 2.1: Communications Loop Performance
Table 2.1: Communications Loop Performance
Table 2.1: Communications Loop Performance
Table 2.1: Communications Loop Performance
Single
Single
Open on
Ground on
Loop
Loop
Style 4 (2-wire) Loop Operation (meets NFPA 72 Style 4 requirements)
Alarm
1
Trouble
Capability
Trouble
Style 6 (4-wire) Loop Operation (meets NFPA 72 Style 6 requirements)
Alarm
Alarm
Capability
Capability
Trouble
Trouble
Style 7 (4-wire) Loop Operation (meets NFPA 72 Style 7 requirements)
Alarm
Alarm
Capability
Capability
Trouble
Trouble
24
Technical Manuals Online! - http://www.tech-man.com
Fault Condition
Loop
Loop
Shorted
Shorted
Shorted
Loop
and
and
Opened
Grounded
Trouble
Trouble
Trouble
2
Trouble
Trouble
Trouble
3
Alarm
Alarm
Capability
Trouble
Capability
Trouble
Trouble
Document # 50428
firealarmresources.com
Loop
Opened
Communication
and
Loss
Grounded
Trouble
Trouble
Alarm
Capability
Trouble
Trouble
Alarm
Capability
Trouble
Trouble
Rev. B1
7/28/97
P/N 50428:B1
Notes:
1. Trouble indicates a trouble
signal will be generated at the
control panel during the abnormal
condition.
2. Alarm Capability indicates an
alarm signal can be transmitted to
the control panel during the
abnormal condition.
3. Loop operation meeting Style 7
requirements isolates entire
physical zone on the communica-
tions loop from faults that occur
within other areas of the loop.

Advertisement

Table of Contents
loading

Table of Contents