Fire-Lite Alarms MS-9200 Technical Manual page 55

Addressable fire control panel (export version)
Table of Contents

Advertisement

As an example, the user could quickly enter 'FLR_3_ROOM_305' as follows:
1) The cursor is on the first letter of the ADJ field. Press the Zero key twice to display 'FLR3'.
2) With the cursor on the first letter of the NOUN field, press the Zero key twice to recall the display
'ROOM304'. The cursor automatically jumps from the first to the last letter of the noun field.
3) With the cursor on the last letter of the NOUN field, press the Zero key again to increment the room
number to 305.
4) Press the Right arrow cursor to advance to the Zone field.
5) Select a zone number from 00 to 56. Z00 (default zone) is the general alarm zone. Z01 through Z56
may be selected to link software zones. Only zones Z01 through Z16 will be displayed on the
optional ZDM-16F LED module.
To load the addressable device's program into memory at any time, press the ENTER key. After pressing
ENTER, autoprogram displays the next new detector. If a detector had been previously entered into memory,
but is missing (no answer), the display shows the following:
If ENTER is pressed, the device is deleted from memory and autoprogram displays the next new device. If the
LEFT CURSOR is pressed, the program is unchanged, and the next new device is displayed.
After all new detectors are presented for editing, the autoprogram feature displays the modules on the SLC loop
starting with the device found at the lowest address.
II. II. II. II. II.
MONITOR MODULE AUTOPROGRAM
MONITOR MODULE AUTOPROGRAM
MONITOR MODULE AUTOPROGRAM
MONITOR MODULE AUTOPROGRAM
MONITOR MODULE AUTOPROGRAM
Monitor Module Autoprogram is similar to Detector Autoprogram. When a new monitor module is presented, a
typical display might be:
The major program editing for monitor modules is the selection of the Type Code on the first line. To change
this selection, use the UP and DOWN cursor keys as the entire field blinks. The default selection is monitor, as
shown in the screen above. Note that selection of a type code may change the functional operation of the
addressable device.
TYPE CODE LABEL
TYPE CODE LABEL
TYPE CODE LABEL
TYPE CODE LABEL
TYPE CODE LABEL
MONITOR
PULL BOX
HEAT DET
SMOKE ZON
WATERFLOW
SUPERVISY
TAMPER_SW
_________
ACK_SW__
SILENC SW
RESET SW
DRILL_
Follow the same procedure as described in Section I New Detectors, for editing of the ADJECTIVE and NOUN
fields.
The default zone selection is Z00 (main circuit board NAC outputs 1 & 2) and may be set to Z01 through Z56 if
desired. See Appendix B Software Zone Assignment.
Technical Manuals Online! - http://www.tech-man.com
PROGRAM SMOKE DET P01
NO ANSWER
PROGRM MONITOR M01
<ADJ><NOUN>
SPECIAL FUNCTION
SPECIAL FUNCTION
SPECIAL FUNCTION
SPECIAL FUNCTION
SPECIAL FUNCTION
NONE (DEFAULT)
NONE
NONE
NONE
CAUSES NON SILENCEABLE ALARM
BECOMES SUPERVISORY POINT (SEE SECTION IV, OPERATION)
BECOMES SUPERVISORY POINT (SEE SECTION IV, OPERATION)
NONE (BLANK LABEL)
FUNCTIONS LIKE ACKNOWLEDGE SWITCH
FUNCTIONS LIKE SILENCE SWITCH
FUNCTIONS LIKE RESET SWITCH
FUNCTIONS LIKE DRILL SWITCH
Document # 50428
Rev. B1
7/28/97
firealarmresources.com
DELETE?
Z00
P/N 50428:B1
55