Fire-Lite Alarms MS-9200 Technical Manual page 42

Addressable fire control panel (export version)
Table of Contents

Advertisement

2.16
2.16
2.16
2.16
2.16
Optional Modules
Optional Modules
Optional Modules
Optional Modules
Optional Modules
The MS-9200 supports option modules, using connectors J6, J11, J12 and J16 on the main board. There are
five optional modules available for the MS-9200; the RTM-8F Relay/transmitter Module, PIM-24 Printer/PC
Interface Module, the UDACT-F Universal Digital Alarm Communicator Transmitter, the DIM-485 LCD-40
Display Interface Module and the ZDM-16F 16 zone LED Module. Jumper JP4 must be cut before installa-
tion of the RTM-8F optional module to enable module placement supervision. Note that devices connected
to the standard EIA-485 connector, the optional EIA-232 connector, the optional EIA-485 connector (via the
PIM-24 or DIM-485) or SLC Loop may be protected from voltage transients by using one of the compatible
surge suppressors listed in Table G-1 of the appendix.
Figure 2.23: Optional Module Location
Figure 2.23: Optional Module Location
Figure 2.23: Optional Module Location
Figure 2.23: Optional Module Location
Figure 2.23: Optional Module Location
UDACT-F Universal Digital Alarm Communicator
UDACT-F Universal Digital Alarm Communicator
UDACT-F Universal Digital Alarm Communicator
UDACT-F Universal Digital Alarm Communicator
UDACT-F Universal Digital Alarm Communicator
Transmitter
Transmitter
Transmitter
Transmitter
Transmitter
Transmits system status to UL Listed Central Station Receivers
via the public switched telephone network. It is capable of
reporting up to 56 software zones or up to 198 addressable
points. The UDACT-F may be mounted directly to the MS-9200
main circuit board, or remotely in a UBS-1F (as shown) or ABS-
8RF enclosure. The MS-9200 requires software P/N 73580 or
higher to support the UDACT-F. For additional information,
refer to the UDACT-F Manual P/N 50050.
42
Technical Manuals Online! - http://www.tech-man.com
MS-9200 Main Circuit Board
MS-9200 Main Circuit Board
MS-9200 Main Circuit Board
MS-9200 Main Circuit Board
MS-9200 Main Circuit Board
Comm
Comm
unicators
unicators
Communicators
Comm
Comm
unicators
unicators
Document # 50428
firealarmresources.com
UBS-1F Enclosure
UBS-1F Enclosure
UBS-1F Enclosure
UBS-1F Enclosure
UBS-1F Enclosure
Rev. B1
7/28/97
P/N 50428:B1
J11 accepts PIM-24 or DIM-485
J12 accepts ZDM-16F
J16 accepts UDACT-F
Cut JP4 for RTM-8F
supervision
J6 accepts RTM-8F