Style 6 Operation
Style 6 Operation
Style 6 Operation
4.13
4.13
Style 6 Operation
Style 6 Operation
If the SLC is wired and programmed for Style 6, and a single fault occurs, the control panel will detect
the fault and drive both ends of the line, fully recovering from the fault. The panel latches the trouble and displays
it until the System Reset switch is pressed. The display shows STYLE 6
4.14
4.14
Read Status
Read Status
4.14
4.14
4.14
Read Status
Read Status
Read Status
Read Status functions do not require a password. The MS-9200 will continue to provide fire protection while in
read status mode . Read status may be entered while in alarm or trouble. If a new alarm or trouble occurs
during these functions, the Read Status is aborted to prevent confusion.
READ STATUS ENTRY
READ STATUS ENTRY
READ STATUS ENTRY
READ STATUS ENTRY
READ STATUS ENTRY
The operator presses the ENTER key, and the LCD display shows:
The operator presses 2, and the display shows:
From this display, an operator may select one of three choices:
• To DISPLAY POINT status, the type of device to be read must first be identified by pressing the (
a detector or the (#) key for a module. The two digit device address is keyed in next, followed by the
ENTER key.
• To DISPLAY ZONE status, press the (
(1-56) and press ENTER. The UP and DOWN cursor keys are used to view the next or previous zone.
• To DISPLAY SYSTEM PARAMETERS, press the (
• To DISPLAY BELL CIRCUIT status, press the (
ENTER.
• To display the 500-event HISTORY file on the LCD, press the 1 key, then ENTER. The UP and
DOWN Arrow keys are used to step through the entries in the file.
• To PRINT PROGRAM CONTENTS and CURRENT SYSTEM STATUS or HISTORY FILE, press the 2 key,
then ENTER. A new Menu appears which prompts to press 1 to print Program/Status or 2 to print History
file.
During this and all subsequent operations except print operations, a two minute timer is started that
will return to the previous display if no key is pressed. Each key press restarts the two minute timer.
Press of the left CURSOR (backspace) deletes the previous entry. If there is no entry, it will abort the
Read Status operation and return to the previous display. System Reset will also abort the Read
Status.
70
Technical Manuals Online! - http://www.tech-man.com
STYLE 6
STYLE 6
STYLE 6
STYLE 6 trouble type.
1=PROGRAMMING
2=RD STATUS 3=AC/BAT
DISPLAY POINT=*/#, AA
HISTORY=1 PRINT=2
*
*
) key, then press the (
) key again. Next, key-in the zone number
*
) key then press the (
*
) key, followed by the (#) key, then the digit 1 or 2, then
Document # 50428
Rev. B1
7/28/97
firealarmresources.com
*
) key again followed by ENTER.
P/N 50428:B1
*
) key for