Download Print this page
Fire-Lite Alarms MS-2 Instructions

Fire-Lite Alarms MS-2 Instructions

Fire alarm control panel

Advertisement

Quick Links

GENERAL
GENERAL
GENERAL
GENERAL
GENERAL
The Fire•Lite MS-2 and MS-2E Fire Alarm Control Panels
bring the latest in microprocessor technology to conven-
tional fire controls. The MS-2 is compatible with the new
i³™
smoke detectors from System Sensor, and provides
such advanced features as drift compensation, mainte-
nance alert, and freeze warning. Automatic synchronization
of audio/visual devices is provided, using three selections
for manufacturer protocol. The NAC protocol includes the
ability to silence audible devices while strobes continue to
flash, using only a single pair of wires.
The MS-2 also is compatible with conventional input de-
vices such as two- and four-wire smoke detectors, pull
stations, waterflow devices, tamper switches and other nor-
mally-open contact devices. For 240 VAC operation, order
MS-2E. See the Fire•Lite Device Compatibility Document
15384 for a complete list of compatible devices.
NOTE: Unless indicated otherwise, the term "MS-2" refers to
both MS-2 and MS-2E models.
FEATURES
FEATURES
FEATURES
FEATURES
FEATURES
• Two Style B (Class B) IDCs (Initiating Device Circuits).
• One Style Y (Class B) NAC (Notification Appliance Circuit).
• 24 VDC.
i³™
Technology features:
— Drift compensation automatically adjusts detector sen-
sitivity and increases resistance to false alarms caused
by dust accumulation.
— Maintenance Alert LEDs (per zone) warn of exces-
sive dirt accumulation, preventing false alarms (meets
NFPA 72 requirements).
— Detector sensitivity is automatically measured by the
detector, which automatically adjusts its sensitivity back
to the factory settings when it becomes more sensitive
due to contaminants settling in the chamber.
— Wireless handheld sensitivity meter eliminates the
need for voltmeters, magnets and a physical connec-
tion to the detector. The reader displays sensitivity in
terms of percent per foot obscuration and provides
text status indication.
— Supervisory LED (per zone) provides warning if a de-
tector senses temperature approaching freezing.
— Special test protocol and LED indication allows quick
test of all detectors without need for a ladder.
• NAC synchronization features:
— Provides synchronization of standard ANSI audible sig-
nals as required by NFPA 72.
— Provides synchronization of ADA compliant strobes
per NFPA 72.
Fire•Lite® Alarms is a Honeywell company.
This document is not intended to be used for installation purposes. We try to keep
our product information up-to-date and accurate. We cannot cover all specific
applications or anticipate all requirements. All specifications are subject to change
without notice.
For more information, contact Fire•Lite Alarms, One Fire-Lite Place, Northford,
Connecticut 06472. Phone: (800) 627-3473, Toll-Free FAX: (877) 699-4105.
February16, 2005
www.firelite.com
S624
— Selectable for System Sensor, Wheelock and Gentex
— Selective Silence feature allows manual silence of
• Silent or Audible Walk Test operation mode commanded
from the front keypad, with automatic return to normal after
one hour of inactivity.
• Alarm verification selectable per zone.
• Each zone may be programmed for supervisory or fire,
with separate red and yellow LEDs.
• Disable switches provided per zone.
• NACs programmable for:
— Silence Inhibit
— Strobe Synchronization
— Selective Silence (horn-strobe mute)
— Temporal or Steady signal
— Silenceable or Nonsilenceable
• Form-C Alarm and Trouble relays.
• 3.0 amps total usable current.
• Optional dress panel (P/N DP-MS2/4).
i³™
is a trademark of System Sensor, a Honeywell company.
MS
MS
-2(E)
-2(E)
MS
MS-2(E)
MS
-2(E)
-2(E)
Fire Alarm Control P
Fire Alarm Control P
Fire Alarm Control P
Fire Alarm Control Panel
Fire Alarm Control P
Section: Conventional
California
State Fire
Marshal
7165-0075:200
MS-2
protocols.
horns while strobes continue to flash on the same NAC.
Auto Silence
DF-52211 • 02/16/05 — Page 1 of 2
DF-52211 • A2-250
anel
anel
anel
anel
MEA
297-01-E
Made in the U.S.A.

Advertisement

loading

Summary of Contents for Fire-Lite Alarms MS-2

  • Page 1 The Fire•Lite MS-2 and MS-2E Fire Alarm Control Panels Marshal bring the latest in microprocessor technology to conven- 297-01-E 7165-0075:200 tional fire controls. The MS-2 is compatible with the new i³™ smoke detectors from System Sensor, and provides such advanced features as drift compensation, mainte- S624 nance alert, and freeze warning.
  • Page 2 Door: 15.342" (38.97 cm) high x 14.677" (37.28 cm) wide x 0.375" (0.95 cm) deep. Backbox: 15.0" (38.10 cm) high x AC Power — TB8 14.5" (36.83 cm) wide x 3.0" (7.62 cm) deep. • MS-2: 120 VAC, 50/60 Hz, 2.3 A BACKBOX MOUNTING BACKBOX MOUNTING BACKBOX MOUNTING...

This manual is also suitable for: