Fire-Lite Alarms MS-9200 Technical Manual page 16

Addressable fire control panel (export version)
Table of Contents

Advertisement

Accessories: LCD Point Annunciator - LCD-40 Remote Fire Annunciator
Accessories: LCD Point Annunciator - LCD-40 Remote Fire Annunciator
Accessories: LCD Point Annunciator - LCD-40 Remote Fire Annunciator
Accessories: LCD Point Annunciator - LCD-40 Remote Fire Annunciator
Accessories: LCD Point Annunciator - LCD-40 Remote Fire Annunciator
(refer to Appendix C for detailed wiring requirements and System Edit in the Programming/Read Status Section of
this manual for information on programming the MS-9200 for annunciator use)
The LCD-40 is a compact, attractive, 40-character backlit LCD fire annuncia-
tor that is capable of displaying English-language text. It mimics the display
on the MS-9200 main control circuit board and will annunciate device type,
point alarm, trouble or supervisory condition, zone assignment plus any
custom alpha labels programmed into the control panel. It also provides
system status LEDs to display Power, Alarm, Trouble and Supervisory
conditions. Additionally, the LCD-40 is capable of performing critical system
functions such as acknowledge, silence, reset and drill, remotely from the
host control panel.
Communication between the control panel and the LCD-40 is accomplished over a serial interface employing the EIA-
485 communication standard (DIM-485 option module required). Up to 32 LCD-40s may be connected to the EIA-485
circuit. The annunciator may be powered from the host FACP or a remote UL listed, filtered, regulated power supply
such as the Fire•Lite FCPS-24FE.
Accessories: LED Zone Type - AFM Series Annunciators
Accessories: LED Zone Type - AFM Series Annunciators
Accessories: LED Zone Type - AFM Series Annunciators
Accessories: LED Zone Type - AFM Series Annunciators
Accessories: LED Zone Type - AFM Series Annunciators
(refer to Appendix D for detailed wiring requirements and System Edit in the Programming/Read Status Section of
this manual for information on programming the MS-9200 for annunciator use)
The AFM Series Annunciators remotely display system status. The AFM/AEM-16AT annunciators display zone alarm
and trouble status. In addition, they provide remote ACKNOWLEDGE, SILENCE, RESET and DRILL functions. The
AFM/AEM-32 annunciators display zone alarm status only and provide no remote system switch functions. For more
detailed information, refer to the appropriate AFM Annunciator manual.
AFM-16ATX
AFM-16ATX
AFM-16ATX
AFM-16ATX
AFM-16ATX
The Annunciator Fixed Module-
16ATX contains 16 red alarm and 16
yellow trouble LEDs, a system
trouble LED, an ON LINE/POWER
LED, and a local piezo sounder with
switches for MS-9200 ACKNOWL-
EDGE, SILENCE, RESET, and
DRILL. The AFM-16ATX is fixed at
address '1' and will accept up to 3
AEM-16ATF Expanders.
AEM-16ATF
AEM-16ATF
AEM-16ATF
AEM-16ATF
AEM-16ATF
The Annunciator Expander Module-
16ATF connects to the AFM-16ATX and
adds 16 sets of red alarm LEDs and yellow trouble
LEDs. Three AEM-16ATFs may be added to an AFM-
16ATX.
AFM-16ATF
AFM-16ATF
AFM-16ATF
AFM-16ATF
AFM-16ATF
The Annunciator Fixed
Module-16ATF contains 16 red
alarm and 16 yellow trouble LEDs, a
system trouble LED, an ON LINE/
POWER LED, and a local piezo
sounder with switches for MS-9200
ACKNOWLEDGE, SILENCE,
RESET, and DRILL. The AFM-
16ATF is fixed at address '1' and
communication is via the EIA-485
data line.
16
Technical Manuals Online! - http://www.tech-man.com
THE AFM-32AX
THE AFM-32AX
THE AFM-32AX
THE AFM-32AX
THE AFM-32AX
The Annunciator Fixed Module-32AX
contains 32 red alarm LEDs, a system
trouble LED, an ON LINE/POWER LED,
and a local piezo sounder with a local
Silence/Acknowledge switch. The AFM-
32AX is fixed at address "1," and will
accept one AEM-32AF expander.
AEM-32AF
AEM-32AF
AEM-32AF
AEM-32AF
AEM-32AF
The Annunciator Expander Module-32AF
connects to the AFM-32AX and adds 32
red alarm LEDs. The AEM-32AF is
identical in frontal appearance to the AFM-
32AX. Only one expander module is allowed.
AFM-16AF
AFM-16AF
AFM-16AF
AFM-16AF
AFM-16AF
The Annunciator Fixed Module-16AF
has 16 red alarm LEDs. Multiple
annunciators may be used by setting
all annunciators to Receive Only,
except the last AFM-16AF in line.
Each annunciator's address is internally fixed
at '1', and communication is via the EIA-485
data line. The Local Silence/Acknowledge
switch functions as local lamp test and silence
for annunciator piezo. LEDs include On
Line and System Trouble indicators.
AFM-32AF
AFM-32AF
AFM-32AF
AFM-32AF
AFM-32AF
The AFM-32AF is similar to the AFM-16AF except it has 32
red alarm LEDs for annunciating up to 32 points.
Document # 50428
Rev. B1
7/28/97
firealarmresources.com
P/N 50428:B1
FIRE ALARM ANNUNCIATOR
ALARM ZONE 1
ALARM ZONE 2
ALARM ZONE 3
ALARM ZONE 4
ALARM ZONE 5
ALARM ZONE 6
ALARM ZONE 7
ALARM ZONE 8
ALARM ZONE 9
ALARM ZONE 10
ALARM ZONE 11
ALARM ZONE 12
ALARM ZONE 13
ALARM ZONE 14
ALARM ZONE 15
ALARM ZONE 16
PRESS
SYSTEM TROUBLE
TO
SILENCE
ON LINE

Advertisement

Table of Contents
loading