SYSTEM RESET
SYSTEM RESET
SYSTEM RESET
SYSTEM RESET
SYSTEM RESET
Pressing the System Reset switch turns off all control modules and Notification Appliance Circuits, tempo-
rarily turns off resettable power to 4-wire detectors, causes an 'All Systems Normal' message to be dis-
played on the LCD, and stores 'System Reset' in the printer and history file. It also turns on all LEDs,
piezo, and LCD display segments as long as SYSTEM RESET is held (lamp test). Any alarm or trouble
that exists after System Reset will resound the system.
4.1
4.1
LED Indicators
LED Indicators
4.1
4.1
4.1
LED Indicators
LED Indicators
LED Indicators
The six LED indicators on the front panel operate as follows:
• AC POWER
• AC POWER
• AC POWER
• AC POWER
• AC POWER
This is a green LED which illuminates if 240 VAC power is applied to the system.
• FIRE ALARM
• FIRE ALARM
• FIRE ALARM
• FIRE ALARM
• FIRE ALARM
This is a red LED that flashes when one or more alarms occur. It illuminates steadily when the AC-
KNOWLEDGE or SILENCE switch is pressed. The Alarm LED turns off when the SYSTEM RESET switch
is pressed.
• SUPERVISORY
• SUPERVISORY
• SUPERVISORY
• SUPERVISORY
• SUPERVISORY
This is a yellow LED that flashes when one or more supervisory conditions occur, such as a sprinkler
valve tamper condition. It illuminates steadily when the ACKNOWLEDGE or SILENCE switch is pressed.
It turns off when SYSTEM RESET is pressed.
• ALARM SILENCE
• ALARM SILENCE
• ALARM SILENCE
• ALARM SILENCE
• ALARM SILENCE
This is a yellow LED that turns on after the ALARM SILENCE key is pressed (preceded by a fire alarm
condition). It turns off when the ALARM ACTIVATE or SYSTEM RESET switch is pressed.
• SYSTEM TROUBLE
• SYSTEM TROUBLE
• SYSTEM TROUBLE
• SYSTEM TROUBLE
• SYSTEM TROUBLE
This is a yellow LED that flashes when one or more trouble conditions occur. It stays on steady when the
ACKNOWLEDGE or SILENCE switch is pressed. The LED turns off when all trouble conditions are cleared.
This LED will also illuminate if the microprocessor watchdog circuit is activated.
4.2
4.2
4.2
4.2
4.2
Normal Operation
Normal Operation
Normal Operation
Normal Operation
Normal Operation
With no alarms or troubles in the system, the display message is " SYSTEMS ALL NORMAL" along with
the current time and date as shown below. To set the time and date, see Section 3.3.04.
The MS-9200 performs the following functions at regular intervals while in normal mode:
• Polls all devices on SLC loop. Checks for valid reply, alarms, troubles, etc.
• Monitors AC input voltage and battery capacity.
• Refreshes LCD display and updates time.
• Scans keyboard.
• Performs detector auto test.
• Tests memory.
• Updates/Reads EIA-485 communications bus.
64