One Fire-Lite Place Northford, CT 06472 Phone: (203) 484-7161 FAX: (203) 484-7118 LCD-40 Series Remote Fire Annunciator for use with Fire•Lite MS-9200(C)/E Addressable Fire Alarm Control Panel Document #50327 1/14/99 Rev: P/N 50327:D1 ECN 99-023 Technical Manuals Online! - http://www.tech-man.com...
Page 2
Adherence to the following will aid in problem-free Installation Precautions installation with long-term reliability: WARNING - Several different sources of power can Like all solid state electronic devices, this be connected to the fire alarm control panel. system may operate erratically or can be damaged Disconnect all sources of power before servicing.
MS-9200(C)/E Addressable Fire Alarm Control Panel. The LCD-40L operates the same as the LCD-40, except it does not have function switches or a key-switch. It should be noted that the LCD-40 Series A nnunciator displays will mimic the LCD display located on the MS-9200 main circuit board.
The LCD-40 Series also provide system status LEDs to display Power, Alarm, Trouble and Supervisory conditions. The LCD-40 is capable of performing system acknowledge, silence, drill and reset remotely while the LCD-40L does not have these features.
LCD-40 Series Annunciators Features of LDC-40 Only Features of LDC-40 Only • Enable/Disable key-switch • Function switches for: Acknowledge Signal Silence Drill System Reset • DIP switches control function switches and key-switch enable/ disable Figure 1-1: Components Note: OPEN (Up)
Page 7
LCD-40 Series Annunciators Wiring to Terminals Figure 1-2: Wiring to Terminals Side view Terminal Block Terminal Block replacement replacement P/N 02108 P/N 02109 + EIA-485 OUT + EIA-485 IN - EIA-485 OUT - EIA-485 IN no connection +24 VDC IN...
SW1 switch settings follow: 1 - On (Down) = Receive/Transmit, Off (up) = Receive Only. Set switch 1 to Off (Up) position for all LCD-40 Series Annuncia- tors except the last (or only) annunciator on the EIA-485 loop. Set...
Page 9
Note: SW 1 DIP switch settings as illustrated in Figure 1-3 are as follows: 1. DIP switch 1: On (Down) - Receive/Transmit. This setting is used for the last or only LCD-40 Series Annunciator on the EIA-485 line 2. DIP switch 2: Used on LCD-40 only - On (Down) = membrane function switches enabled.
(3,000 feet [900 m] maximum to last LCD-40). Circuit is power- limited. 2. Up to 32 LCD-40 Series Annunciators may be used on the EIA-485 circuit. The MS-9200 can power a maximum of five annunciators. If additional annunciators are connected, the Fire•Lite FCPS-24F may be used to supply additional power.
MS-9200 main circuit board LCD display with the following exceptions: • Upon Power-up, the LCD-40 Series may display the following message until a valid message is received from the MS-9200 • If an LCD-40 Series Annunciator fails to receive communica-...
Operation Switch Functions for LCD-40 Only Switch Functions for LCD-40 Only 2.2.1 Key-switch Key-switch (shown in Off position) The key-switch is used to enable and disable the operation of the function switches if switch 2 on DIP switch SW1 has been placed to the On (Down) position.
Operation Switch Functions for LCD-40 Only LEDs to steady on. The second press of the switch stops the scroll- ing and holds the event on the display for one minute. Subsequent pressing of the switch 'steps' through each active event. 2.2.3 Silence When the Silence switch is pressed and released, the LCD-40 sends a signal silence command to the control panel.
It stays on steady when an Acknowledge or Silence switch is pressed. The LED turns off when all trouble conditions are cleared. This LED will also illuminate if the microprocessor watch- dog circuit within the LCD-40 Series is activated. Document 50327 Rev D1 1/14/99 P/N 50327:D1 Technical Manuals Online! - http://www.tech-man.com...
Series electrical box, must be connected to earth ground! Never use the shield for grounding purposes. To mount the LCD-40 Series Annunciators in an electrical box, the trim ring must first be removed. The trim ring is held in place by two screws inserted through the top and bottom edge as illustrated in Figure 3-1.
Page 16
Mounting Hardware and Backboxes Figure 3-2: Hardware and Backboxes LCD-40 Series flange LCD-40 Series Trim Ring (replacement P/N 23165) 3-Gang Electrical Box P/N 10103 (semi-flush mount) 3-Gang Electrical Box P/N SBB-3 (surface mount) Document 50327 Rev D1 1/14/99 P/N 50327:D1 Technical Manuals Online! - http://www.tech-man.com...
Figure 3-3: Semi-flush Mounting LCD-40 Series flange Mounting holes (4) CAUTION! The LCD-40 Series can ONLY be semi-flush mounted in a three-gang electrical box, P/N 10103 or equivalent, with a minimum depth of 2 3/16". The LCD-40 Series cannot be mounted in three gangable electrical switch boxes connected together.
ONLY be surface mounted in a three- gang electrical box, P/N SBB-3 or equivalent, with a minimum depth of 2.75". The LCD-40 Series cannot be mounted in three gangable electrical switch boxes connected together. Three-gang electrical box P/N SBB-3 or equivalent with a 2.75"...
The LCD-40 Series Annunciators can be powered by the MS-9200 (refer to the MS-9200 Technical Manual for the proper connection of the LCD-40 Series) or from a remote UL listed, filtered power supply such as the Fire•Lite FCPS-24F. The power run to the annunciator must...
Page 20
Notes: 1. All connections are power-limited and supervised 2. A maximum of 32 LCD-40 Series annunciators may be con- nected to this circuit 3. 6,000 feet (1,800 m) maximum distance @ 18 AWG (0.75 mm between the panel, annunciators and return to the panel.
Page 21
1. Terminal to terminal wiring is shown between the DIM-485 and one LCD-40 Series Annunciator 2. If more than one LCD-40 Series Annunciator is installed, the wiring to the DIM-485 In (+) Terminal 2 and In (-) Terminal 4 will be from the last installed annunciator (refer to Figure 4-4 on page 22) 3.
Page 22
J11 being careful not to bend any pins 3. Be certain to secure the DIM-485 module to the MS-9200 and to keep all wiring from mechanically interfering with the module. Figure 4-4: Wiring FACP to LCD-40 Series LCD-40 Series in grounded box Ferrite Core P/N FBD-1...
, motor control circuits or SCR power circuits. Note: To ensure static (ESD - electrostatic discharge) protection, all enclosures, including the LCD-40 Series electrical box, must be connected to earth ground! Never use the EIA -485 shield for this purpose. The EIA -485 shield is for radiated noise emission protection (RFI, EMI).
Page 24
EIA-485 Shield Termination EIA-485 Without Conduit Figure 5-1: EIA-485 Without Conduit Connect the drain wire to the outside of the MS-9200 cabinet via a BX-type connector. Shield Drain Wire (+) EIA-485 (-) EIA-485 FACP Backbox FACP Document 50327 Rev D1 1/14/99 P/N 50327:D1 Technical Manuals Online! - http://www.tech-man.com firealarmresources.com...
2) Twisted, shielded wire is recommended for the EIA-485 communications loop 3) Each LCD-40 Series electrical backbox is connected to earth ground via the conduit 4) Shield is connected to the FACP cabinet (earth ground) leaving and entering the FACP...
Use the left and right arrow keys to move to the L/P option. Once at the L/P option, to enable the LCD-40 Series Annunciator option, use the up and down arrow keys to scroll to the L (for LCD-40 Series Annunciator) choice. The LCD-40 Series can now communicate with the MS-9200.
Page 28
Limited Warranty ® Fire•Lite warrants its products to be free from defects in materials and workmanship for eighteen (18) months from the date of manufacture, under normal use and service. Products ® are date stamped at time of manufacture. The sole and exclusive obligation of Fire•Lite is to repair or replace, at its option, free of charge for parts and labor, any part which is defective in ®...