Fire-Lite Alarms MS-9200 Technical Manual page 50

Addressable fire control panel (export version)
Table of Contents

Advertisement

NOTE: There are two programming levels. Program Level 1 is for system configuration in which data relating
to device types, zoning, messages, etc. is entered into the system memory. Program Level 2 is where a
qualified operator can access features such as Disable, Clear History, Walktest, Time Change and Program
Check. For Program Level 2, the SW1 Write Protect switch should remain in the up (Write Protect) position.
2 = Read Status: Entering Read Status allows the user to read the status of any point/zone in the system plus
display or print the history file or print the entire user program. The Read Status feature is NOT password
protected. Read Status is explained in Section IV Operating Instructions.
3 = AC/BAT: Entering AC/BAT allows the user to read the battery voltage and AC line voltage. The AC/BAT feature
is NOT password protected.
Section 3.1 on the following page describes initial programming procedures for a new system. The same
procedures are used to modify programming in an existing system. Make certain the SW1 Write Protect switch
is in the down position before attempting any Level 1 Programming functions.
3.0 Initial Po o o o o w w w w w er-up
3.0 Initial P
3.0 Initial P
3.0 Initial P
3.0 Initial P
Once wiring of addressable devices to the SLC loop is completed, power up the system. Since the addressable
devices have not yet been programmed, their LEDs will not flash, the System Trouble LED will be on and the LCD
display will alternate between the following two displays:
If the system remains unprogrammed, the piezo will sound after a few minutes. It can be silenced by pressing the
Acknowledge/Step switch, but it will continue to resound until the system is programmed.
50
Technical Manuals Online! - http://www.tech-man.com
er-up
er-up
er-up
er-up
TROUBLE IN SYSTEM
PROGRAM CORRUPTED
TROUBLE IN SYSTEM
NO DEVICES INSTALL
Document # 50428
firealarmresources.com
BATTERY: 24V
AC LINE: 240V
Rev. B1
7/28/97
P/N 50428:B1