The UDACT-F may be mounted directly to the MS-9200 main circuit board
or remotely in an ABS-8RF or UBS-1F enclosure up to 6,000 feet away
from the control panel. All power must be removed from the Control Panel
before making any connections to prevent circuit damage. The EIA-485
serial interface is connected between the Control Panel and UDACT-F using
twisted, shielded pair wire. Power should be wired from the Control Panel's
24VDC (nominal) filtered, nonresettable output to TB1 on the UDACT-F
(except when mounted in the MS-9200).
Mounting Inside MS-9200 Enclosure
Mounting Inside MS-9200 Enclosure
Mounting Inside MS-9200 Enclosure
Mounting Inside MS-9200 Enclosure
Mounting Inside MS-9200 Enclosure
The MS-9200 must have firmware with a Part Number of 73580 or higher installed to allow use of the UDACT-F.
Remove all power from the MS-9200 by disconnecting AC and batteries. Install the supplied standoffs (three
nylon and one aluminum standoff) in the appropriate holes located on the right side of the MS-9200 main circuit
board as illustrated in Figure 2.25. Position J10, located on the back of the UDACT-F, over connector J16 which
is located center right on the main MS-9200 circuit board, and carefully connect. Secure the UDACT-F to the
aluminum standoff with the screw provided. Caution: Damage can occur if female connector J10 is not properly
aligned with male connector J16.
The EIA-485 circuit and 24VDC power are provided directly from connector J16 of the MS-9200. Note: A 120
ohm EOL resistor is not required on the UDACT-F EIA-485 terminals when it is installed inside the MS-9200
cabinet. The EOL resistor is required at the last device on the EIA-485 line external to the MS-9200 panel.
Programming
Programming
Programming
Programming
Programming
Refer to System Edit in the Programming/Read Status Section of this manual for information on programming
the MS-9200 to function with the UDACT-F.
Technical Manuals Online! - http://www.tech-man.com
MS-9200
3/4" aluminum standoff
with nut required for
transient protection
3/4" Nylon
Standoffs
Figure 2.25: UDACT-F Mounting to MS-9200
Figure 2.25: UDACT-F Mounting to MS-9200
Figure 2.25: UDACT-F Mounting to MS-9200
Figure 2.25: UDACT-F Mounting to MS-9200
Figure 2.25: UDACT-F Mounting to MS-9200
Document # 50428
Rev. B1
firealarmresources.com
Figure 2-24: ABS-8RF Enclosure
Figure 2-24: ABS-8RF Enclosure
Figure 2-24: ABS-8RF Enclosure
Figure 2-24: ABS-8RF Enclosure
Figure 2-24: ABS-8RF Enclosure
UDACT-F
7/28/97
P/N 50428:B1
43