The M302 Monitor Module
The M302 Monitor Module
2.12 The M302 Monitor Module
2.12
2.12
The M302 Monitor Module
The M302 Monitor Module
The M302 Monitor Module is an addressable module that interfaces and monitors UL compatible conventional 2-wire
smoke detectors. (See Fire-Lite Compatibility Document P/N 15384.) The supervised circuit may be wired as NFPA
Style B or D.
COMMUNICATIONS SLC LOOP CONNECTIONS
COMMUNICATIONS SLC LOOP CONNECTIONS
COMMUNICATIONS SLC LOOP CONNECTIONS
COMMUNICATIONS SLC LOOP CONNECTIONS
COMMUNICATIONS SLC LOOP CONNECTIONS
Connect the MS-9200 Communications SLC loop to M302 terminals 1(-) and 2(+). The M302 occupies one module
address on the loop. Use rotary switches on the M302 to set the module to the required loop address.
NFPA STYLE B INITIATING DEVICE CIRCUIT
NFPA STYLE B INITIATING DEVICE CIRCUIT
NFPA STYLE B INITIATING DEVICE CIRCUIT
NFPA STYLE B INITIATING DEVICE CIRCUIT
NFPA STYLE B INITIATING DEVICE CIRCUIT
Connect 2-wire smoke detectors to M302 terminals 6 (B-) and 7 (B+) (as shown in Figure 2.16). IDC installation
wiring must not exceed 25 ohms, 12-18 AWG wire. Use a 3.9K ELR across the last initiating device. (See Figure
2.16).
NFPA STYLE D INITIATING DEVICE CIRCUIT
NFPA STYLE D INITIATING DEVICE CIRCUIT
NFPA STYLE D INITIATING DEVICE CIRCUIT
NFPA STYLE D INITIATING DEVICE CIRCUIT
NFPA STYLE D INITIATING DEVICE CIRCUIT
Connect 2-wire smoke detectors to M302 terminals 6 (B-) and 9 (D-), 7 (B+) and 8 (D+) (as shown in Figure 2.17).
IDC installation wiring must not exceed 25 ohms, 12-18 AWG wire. (See Figure 2.17).
POWER CONNECTIONS
POWER CONNECTIONS
POWER CONNECTIONS
POWER CONNECTIONS
POWER CONNECTIONS
Power must be switched 24VDC isolated regulated and battery backed. Connect to M302 terminals 3 (-) and 4 (+)
(as shown in Figures 2.16 and 2.17).
NOTES ON M302 MONITOR MODULE
NOTES ON M302 MONITOR MODULE
NOTES ON M302 MONITOR MODULE
NOTES ON M302 MONITOR MODULE
NOTES ON M302 MONITOR MODULE
1. IDC and power connections are supervised by the M302 and reported to the MS-9200
2. Maximum current in alarm is 90 mA power limited
3. See Appendix F for device specifications
4. See Appendix A for power supply calculations
TEST SWITCH
TEST SWITCH
TEST SWITCH
TEST SWITCH
TEST SWITCH
The M302 includes a magnetic test switch sensor located near the center front of the module. Activation of this
switch by test magnet P/N M02-04-00 will cause an open circuit indication in the Style B/D loop.
32
Technical Manuals Online! - http://www.tech-man.com
4
4
5
5
3
3
6
6
2
2
7
7
1
1
8
8
0
0
9
9
Document # 50428
Rev. B1
7/28/97
firealarmresources.com
Status LED
Rotary Decade
Address Switches
Magnet Test Position
P/N 50428:B1