The MS-4412B/MS-4424B(E)
FIRE ALARM CONTROL PANELS
DOCUMENT 15125
F1
06/24/97
Rev:
12 Clintonville Road, Northford CT 06472
ECN 97-192
Technical Manuals Online! - http://www.tech-man.com
firealarmresources.com

Advertisement

Table of Contents
loading

Summary of Contents for Fire-Lite Alarms MS-4412B

  • Page 1 The MS-4412B/MS-4424B(E) FIRE ALARM CONTROL PANELS DOCUMENT 15125 06/24/97 Rev: 12 Clintonville Road, Northford CT 06472 ECN 97-192 Technical Manuals Online! - http://www.tech-man.com firealarmresources.com...
  • Page 2 Technical Manuals Online! - http://www.tech-man.com firealarmresources.com...
  • Page 3: Table Of Contents

    Table of Contents I NFPA Standards ...............4 II Additional Information ............4 1.0 The MS-4412B/MS-4424B(E) ............. 5 1.1 Features....................... 5 1.2 Circuits ......................... 5 1.3 Optional Boards ....................7 1.4 Remote Annunciator .................... 8 1.5 Specifications ...................... 9 2.0 System Operation ................11 2.1 System Status LEDs ..................
  • Page 4: Infpa Standards

    Applicable Local and State Building Codes Requirements of the Local Authority Having Jurisdiction Noti•Fire 911A Manual, Document 74-06200-005 MS-5012 Manual, Document 15465 Fire•Lite Device Compatibility Document, 15384. ADA Americans with Disabilities Act MS-4412B/MS-4424B 15125:F1 06/24/97 Technical Manuals Online! - http://www.tech-man.com firealarmresources.com...
  • Page 5: The Ms-4412B/Ms-4424B(E)

    1.0 The MS-4412B/MS-4424B(E) Features Microprocessor-controlled. Complies with NFPA 72-1993 Proprietary Fire Alarm Systems (requires Potter EFT-C McCulloh Power-limited on all circuits except Transmitter). Municipal Box Output and the relay output. One Man Walk Test. Alarm and trouble resound. Disable/enable controls per Initiating Device Circuit.
  • Page 6 Figure 1.0-1: MS-4412B/MS-4424B(E) Installation Diagram MS-4412B/MS-4424B 15125:F1 06/24/97 Technical Manuals Online! - http://www.tech-man.com firealarmresources.com...
  • Page 7: Optional Boards

    Optional Boards The MS-4412B/MS-4424B(E) has mounting slots for two option boards. Any two of the following three option modules may be installed. (see Section "Optional Modules" ) Transmitter Module (4412TM, 12V; 4XTMF, 24V) The Transmitter Module provides a supervised output for local energy...
  • Page 8: Remote Annunciator

    Notes: The Remote Annunciator requires the use of an LED Interface module (4412LM/ 4XLMF). When used with the MS-4412B, the RZA-4XF must be installed in the same room or within 20 ft. of the control panel. MS-4412B/MS-4424B 15125:F1 06/24/97 Technical Manuals Online! - http://www.tech-man.com...
  • Page 9: Specifications

    Short circuit current: 40 mA maximum Maximum detector current in standby: 2 mA (max) per zone Maximum loop resistance: MS-4412B: 100 ohms / MS-4424B: 200 ohms End-of-line resistor: MS-4412B: 2.2K, 1/2-Watt (part # R-2.2K UL listed) MS-4424B(E): 4.7K, 1/2-Watt (part # 71252 UL listed) Detector loop current is sufficient to ensure operation of one alarmed detector per zone.
  • Page 10 Cabinet = 3.047" Backbox = 3.0" Door = 14.718" Backbox = 14.5" Door = 14.218" Backbox = 14" Optional Trim Ring (TR-2-R) Figure 1.5-1: Cabinet Dimensions MS-4412B/MS-4424B 15125:F1 06/24/97 Technical Manuals Online! - http://www.tech-man.com firealarmresources.com...
  • Page 11: 2.0 System Operation

    Yellow LED that illuminates steadily on motherboard during a ground fault condition (not visible through door). MICRO FAIL Yellow LED that Illuminates on motherboard when watchdog timer detects microproces- sor failure (not visible through door). MS-4412B/MS-4424B 15125:F1 06/24/97 Technical Manuals Online! - http://www.tech-man.com firealarmresources.com...
  • Page 12: Control Switches

    Note: If zone 4 is set for supervisory, the red alarm ZONE 2 LED is not used. TROUBLE LED ALARM LED ZONE 3 TROUBLE LED ALARM LED ZONE 4 TROUBLE LED MS-4412B/MS-4424B 15125:F1 06/24/97 Technical Manuals Online! - http://www.tech-man.com firealarmresources.com...
  • Page 13: Supervisory

    ACTIVATE switch, and then the ALARM SILENCE switch. 3) Last Event is displayed. 4) Release the TONE SILENCE switch to return to normal operation. 5) To clear the Last Event buffer, press RESET twice. MS-4412B/MS-4424B 15125:F1 06/24/97 Technical Manuals Online! - http://www.tech-man.com firealarmresources.com...
  • Page 14: 3.0 Installation Procedure

    0.25" away from any non-power limited circuit wiring. Furthermore, all power limited circuit wiring and non-power limited circuit wiring must enter and exit the cabinet through different knockouts and/or conduits. A typical wiring diagram for the MS-4412B/MS-4424B(E) is shown below.
  • Page 15: Initiating Device Circuits

    Pull Station Tamper Switch IDC #1 IDC #2 IDC #3 IDC #4 Figure 3.2-1: Example of Initiating Device Circuits * For the MS-4412B, use UL listed 2.2K, 1/2-Watt ELRs (part # R-2.2K) MS-4412B/MS-4424B 15125:F1 06/24/97 Technical Manuals Online! - http://www.tech-man.com firealarmresources.com...
  • Page 16: 4-Wire Smoke Detector Connections

    IDC(-) UL Listed UL-listed 24 VDC Listed Four-Wire Smoke Detectors Power (12 VDC for the MS-4412B) Supervision Relay IDC #1 Style B Initiating Device Circuit A maximum of 200mA is available from the Initiating Device Circuits 1, 2, 3, or 4 voltage for 4-wire smoke detector power can be used.
  • Page 17: Output Circuits

    If a 4412ZM/4XZMF Relay Module is used, relay 4 will activate for supervisory conditions. If an RZA-4XF is used, the red LED 4 will annunciate supervisory conditions. Jumper Configuration Table for MS-4412B and MS-4424B r a l Note: The Table remains the same with Dip Switch #3 in either state.
  • Page 18 12V panel OUT #1 OUT #2 SUPV1 SUPV2 Figure 3.4-1: Notification Appliance Circuits ALARM TROUBLE NO NC C NO NC C +VNR Alarm Trouble Figure 3.4-2: Alarm / Trouble Coils and Contacts MS-4412B/MS-4424B 15125:F1 06/24/97 Technical Manuals Online! - http://www.tech-man.com firealarmresources.com...
  • Page 19: Power

    Figure 3.5-1: Diagram of Power Terminals AC Power Primary power required for MS-4412B and MS-4424B is 120 VAC, 50/60 Hz, 1.2 amps and primary power required for the MS-4424BE panel is 220/240 VAC, 50 HZ. 0.6 amps. Overcurrent protection for this circuit must comply with Article 760 of the National Electrical Code (NEC) and/or local codes.
  • Page 20: Optional Modules

    Optional Modules The MS-4412B/MS-4424B(E) has two module connectors - J5 and J8. Three modules are available for the panel and they can be used in any combination, including duplicate modules (see notes below). The corresponding option jumper must be cut before installation of an optional module, to enable module supervision.
  • Page 21 Affix the terminal identification labels provided with the option modules as shown below. (Part # 42050) Standoffs Option Board Main Board Figure 3.6-2: Installing Option Modules MS-4412B/MS-4424B 15125:F1 06/24/97 Technical Manuals Online! - http://www.tech-man.com firealarmresources.com...
  • Page 22 Transmitter Module -- 4XTMF (MS-4412B: 4412TM) Polarities shown in activated positions. The wiring of this module must follow the requirements as specified in the "General" Section, "UL Power Limited Wiring Requirements." Remote Alarm Power Limited Circuit Remote Trouble No Connection...
  • Page 23 Zone Relay Module -- 4XZMF (MS-4412B: 4412ZM) Non-power limited and power limited wiring must have a minimum distance of 0.25" wire to wire. If this module is used to drive non-power limited and power limited circuits, please follow the instructions below: Relay #1 through #4 will activate with Output #1 through #4 and remain latched unless jumper "LATCH"...
  • Page 24 The wiring of this module must follow the requirements as specified in the "General" Section, "UL Power Limited Wiring Requirements." When used with the MS-4412B, The RZA-4XF must be installed in the same room or within 20 feet of the control panel.
  • Page 25: Dip Switch Location And Descriptions

    Zone supervisory LED. Notification Appliance Cir- Trouble LED. cuits 1 and 2 will activate (see Section 3.4). Note: The Reset key must be depressed after any switch configuration has been made. MS-4412B/MS-4424B 15125:F1 06/24/97 Technical Manuals Online! - http://www.tech-man.com firealarmresources.com...
  • Page 26: Appendix A: Battery Calculations

    Place subtotal here : Sum Column for Standby Battery Current and continue to Table A-2. Note: (113 mA maximum for 60 hours of standby) (230 mA maximum for 24 hours of standby) MS-4412B/MS-4424B 15125:F1 06/24/97 Technical Manuals Online! - http://www.tech-man.com firealarmresources.com...
  • Page 27 Select a battery with an equal or greater AH rating than the figure obtained in Table A-2. Batteries must be lead-acid type. Batteries available from Fire•Lite Alarms: PS-1270 - 12 volt, 7 AH (two required for MS-4424B(E); one required for MS-4412B) PS-12120 - 12 volt, 12 AH (two required for MS-4424B(E); one required for MS-4412B) Notes: Alarm AH assumes a maximum system draw of 2.4 amps in alarm for 5 minutes...
  • Page 28: Appendix B: Nfpa Standard-Specific Requirements

    The minimum system components required for compliance with the appropriate NFPA standard are listed below. MS-4412B/MS-4424B(E) Control Panel containing the main control board, cabinet (backbox and door), main supply transformer and power supply. Batteries (refer to Appendix A for Standby Power Requirements).
  • Page 29 Maximum loop resistance allowed for wiring from control panel to Municipal Box is 3 ohms. Municipal Box Circuit Gamewell Model M34-56 Local Energy Municipal Box Note: Municipal Box wiring can leave the building. 4412TM/4XTMF Transmitter Module (activated polarities shown) MS-4412B/MS-4424B 15125:F1 06/24/97 Technical Manuals Online! - http://www.tech-man.com firealarmresources.com...
  • Page 30 Fire•Lite RS82-9 Remote Station Receiver UL listed + - + - Remote Alarm Remote Trouble Note: Remote Alarm and Remote Trouble wiring can leave the building. 4412TM/4XTMF Transmitter Module (activated polarities shown) MS-4412B/MS-4424B 15125:F1 06/24/97 Technical Manuals Online! - http://www.tech-man.com firealarmresources.com...
  • Page 31 Notes: 1) The Maximum standby load shall be 125 mA. 2) The Standby Battery Requirement: 24VDC, 7AH Max. 3) The MS-4412B does not support Noti•Fire 911A. 4) The 911A was discontinued Effective 10/96, this diagram is for reference only. Use the battery positive wire provided with 911A 911A 27.6 VDC (+)
  • Page 32 Place jumper over pins 2 & 3, marked DACT, when employing a DACT. This directs the control panel to transmit all trouble conditions except AC LOSS. y l l y l l y l l MS-4412B/MS-4424B 15125:F1 06/24/97 Technical Manuals Online! - http://www.tech-man.com firealarmresources.com...
  • Page 33 AC POWER TROUBLE ALARM SUPERVISORY RESET SILENCE MODE yellow Black 120 VAC yellow 12VDC Battery Neutral 2-7AH Black Ground White Green AC Wiring for DACT/FACP must be connected to the same circuit. MS-4412B/MS-4424B 15125:F1 06/24/97 Technical Manuals Online! - http://www.tech-man.com firealarmresources.com...
  • Page 34 This control panel/transmitter arrangement can be employed for NFPA 72-1993 Proprietary Fire Alarm System. TROUBLE RESET ALARM MS-4412B/MS-4424B Notes: Form-C Trouble contact which will automatically activate on any Trouble condition. Form-C Alarm contact programmed to activate on General Alarm. MS-4412B/MS-4424B 15125:F1 06/24/97 Technical Manuals Online! - http://www.tech-man.com firealarmresources.com...
  • Page 35: Trouble Shooting Table

    ) s l c r i t i u c r i t i u l i a o l l r c i c r i t i u MS-4412B/MS-4424B 15125:F1 06/24/97 Technical Manuals Online! - http://www.tech-man.com firealarmresources.com...
  • Page 36 Limited Warranty Fire-Lite ® warrants its products to be free from defects in materials and workmanship for eighteen (18) months from the date of manufacture, under normal use and service. Products are date stamped at time of manufacture. The sole and exclusive obligation ®...