Enter the Level 2 password (default = 11111) then press the ENTER key to access Programming Change Level
Two. The screen below will appear:
From this screen, the available function choices include point DISABLE, CLEAR HISTORY, WALKTEST, SET
TIME and CHECK programming.
3.3.01 Disable
3.3.01
3.3.01
3.3.01
3.3.01
Disable
Disable
Disable
Disable
Pressing '1' displays the following screen:
*
Press the
key to display detectors, the # key to display modules, followed by the device address, then the
ENTER key. A typical display is shown below:
A point is then displayed on the screen similar to a Point Edit display but with the current status label (ENABLE)
blinking. The current status label may show: NORMAL, TROUBL, DISABL, ALARM, ACTIVE, PROGRM, TEST 01,
ON, OFF. The status label can be changed to DISABL or back to its present status by pressing the UP or DOWN
keys. The disable status is entered/stored in memory by pressing ENTER. The display then returns to the DIS-
ABLE/ENABLE screen shown above. The operator may then enter a new point number, or may press UP/DOWN
to bring up the next lower/higher address point. The disabling of initiating devices that are in alarm or control
points that are ON occurs after the RESET key is pressed.
All disabled points will scroll on the LCD display and the system will remain in trouble until all programmed points
are enabled.
3.3.02 Clear History
3.3.02
3.3.02
3.3.02
3.3.02
Clear History
Clear History
Clear History
Clear History
Pressing '2' displays the following screen:
Press the ENTER key to clear the 500-event History file. Press the left cursor key (Backspace) to exit without
clearing the History file. Caution: Pressing Enter will clear all History events associated with this panel. Care
should be taken to ensure this is the appropriate action.
60
Technical Manuals Online! - http://www.tech-man.com
1=DISABL 2=CLR HIST
3=WALK 4=TIME 5=CHEK
DISABLE/ENABLE
PRESS */#, AA, ENTER
ENABLE
SMOKE DET P01
NORTH BASEMENT Z01
ENTER TO CLEAR HIST.
BACKSPACE TO ESCAPE