Fire-Lite Alarms MS-9200 Technical Manual page 58

Addressable fire control panel (export version)
Table of Contents

Advertisement

There are nine system function options for software P/N 73750 or greater. The factory default selections and user
option selections are shown below:
FUNCTION
V = Alarm Verification (N)one
I = Silence Inhibit
A = Auto-Silence
P = Pre-signal
C = Bell Code
A/U = Annunciators
with or without UDACT-F
L/P = LCD-40 or
Printer/PC in use
S = SLC loop style
R = Alarm/Trouble
Reminder
1
Requires prior approval of Local Authority Having Jurisdiction.
2
When the UDACT-F has a fault, this entry allows the FACP to display 'DACT Trouble' on the LCD display and printer
hardcopy. The history file will also be updated with this information. For zone annunciation use AFM Series Annunciators
or LDM Series Annunciators. For 198 point annunciation, use the LDM Series Annunciators.
3.2.05
3.2.05
3.2.05
Password Change
Password Change
Password Change
3.2.05
3.2.05
Password Change
Password Change
While displaying the Program Menu, press '4' to change either of two passwords. One high level password,
defaulted to 00000, allows for point and system programming. A second lower level password, defaulted to
11111, allows for status changes such as: (1) disable points/zones (2) clear history file, (3) walk test enable,
(4) time and date set and (5) program check. Pressing '4' will display:
Select the password to change by typing
password is entered it is displayed. When ENTER is pressed, the display reads "PRESS ENTER IF OK,
NNNNN = NEW PROGRAM PW". After ENTER is pressed, the new password is stored in EEPROM memory
and the program returns to the program change screen. If BACKSPACE is entered, the password remains
unchanged and the program returns to the program change screen.
58
Technical Manuals Online! - http://www.tech-man.com
DEFAULT
SELECTION
(Y)120 seconds
(N)one
(Y)60 seconds
(N)one
(Y)10 minutes
(N)one
(Y)3 minutes with 15 second Acknowledge
(N)one
(M) = March Time
(T) = Temporal
(C) = California
(N)one
(Z) = 56 Zones
(ZU) =56 Zones Annunciator with UDACT-F
(P) = 198 Points
(PU) = 198 Points Annunciator with UDACT-F
(N)one
L = LCD-40 installed (requires DIM-485)
P = Printer or local PC installed (requires PIM-24)
(4) = Style 4
(6) = Style 6
(N)o
(Y)es = Sound onboard piezo every 15 seconds during alarm and
every 2 minutes during trouble after acknowledge or silence key
has been pressed.
*,NNNNN, E=LEVEL 1 PW
#,NNNNN, E=LEVEL 2 PW
*
or #, then enter the new password. As the new program or status
Document # 50428
Rev. B1
firealarmresources.com
1
1
7/28/97
P/N 50428:B1
1
2
2