3.2.04
3.2.04
System Edit
System Edit
3.2.04
3.2.04
3.2.04
System Edit
System Edit
System Edit
The System Edit function is selected by pressing '3'. The system edit screen appears as shown below for software
releases prior to P/N 73750. This software does not support the LCD-40 Annunciator:
Use the Up and Down arrow keys to scroll through the choices for each option and the Left and Right arrow keys to
move from option to option.
There are eight system function options for software releases prior to P/N 73750. The factory default selections
and user option selections are shown below:
FUNCTION
VF = Alarm Verification (N)one
SI = Silence Inhibit
AS = Auto-Silence
PS = Pre-signal
CD = Bell Code 1
Note: Bell 2 is fixed steady
AN = Annunciators
ST = SLC loop style
REM = Alarm/Trouble (N)o
Reminder
1
Requires prior approval of Local Authority Having Jurisdiction.
2
When the UDACT-F has a fault, this entry allows the FACP to display 'DACT Trouble' on the LCD display and printer
hardcopy. The history file will also be updated with this information. For zone annunciation, up to 56 zones, use AFM
Series Annunciators or LDM Series Annunciators. For 198 point annunciation, use the LDM Series Annunciators.
The system edit screen appears as shown below for software P/N 73750 or greater. This software is required to
support the LCD-40 Annunciator:
Technical Manuals Online! - http://www.tech-man.com
VF=N SI=N AS=N PS=N
CD=N AN=N ST=4 REM=N
DEFAULT
SELECTION
(Y)120 seconds
(N)one
(Y)60 seconds
(N)one
(Y)10 minutes
(N)one
(Y)3 minutes with 15 second Acknowledge
(M)arch Time
(N) = None
(T) = Temporal
(C) = California
(N)one
(Z) = 56 Zones
(ZU) =56 Zones Annunciator with UDACT-F
(P) = 198 Points
(PU) = 198 Points Annunciator with UDACT-F
(4) = Style 4
(6) = Style 6
(Y)es = Sound onboard piezo every 15 seconds during alarm and
every 2 minutes during trouble after acknowledge or
silence key has been pressed.
V=N I=N A=N P=N C=N
A/U=N L/P=N S=4 R=N