Specifications - Fire-Lite Alarms MS-9200 Technical Manual

Addressable fire control panel (export version)
Table of Contents

Advertisement

1.2

1.2 Specifications

1.2
1.2
1.2
Specifications
Specifications
Specifications
Specifications
AC POWER - TB8
AC POWER - TB8
AC POWER - TB8
AC POWER - TB8
AC POWER - TB8
240 VAC, 50 Hz, 1.2 amps
Wire size: minimum #14 AWG with 600V insulation
BATTERY (LEAD ACID ONLY) - J3
BATTERY (LEAD ACID ONLY) - J3
BATTERY (LEAD ACID ONLY) - J3
BATTERY (LEAD ACID ONLY) - J3
BATTERY (LEAD ACID ONLY) - J3
Maximum Charging Circuit:
Maximum Battery Capacity:
COMMUNICATION LOOP - TB6
COMMUNICATION LOOP - TB6
COMMUNICATION LOOP - TB6
COMMUNICATION LOOP - TB6
COMMUNICATION LOOP - TB6
15 VDC nominal, 27.6 volts DC max. Maximum length is 10,000 ft. total twisted pair length. Maximum loop
current is 250mA (Max short circuit) or 100 mA (normal). Maximum loop resistance is 40 ohms. SLC is
supervised and power-limited.
Note: The Communication Loop may leave the protected premises provided an approved surge suppressor
is use (refer to Table G-1 in Appendix).
NOTIFICATION APPLIANCE CIRCUITS - TB1 & TB2
NOTIFICATION APPLIANCE CIRCUITS - TB1 & TB2
NOTIFICATION APPLIANCE CIRCUITS - TB1 & TB2
NOTIFICATION APPLIANCE CIRCUITS - TB1 & TB2
NOTIFICATION APPLIANCE CIRCUITS - TB1 & TB2
Non-regulated special purpose power
Power-limited circuitry
Maximum Voltage Drop in wiring: 2.0V
Operating Voltage Range: 18V to 30V
Current for all external devices: 3.0 amperes expandable to 6.0 amperes
Current Limit: Fuseless, electronic, power-limiting circuitry.
Max. signaling current/circuit: 2.50 amps
End-of-line resistor: 4.7KW , 1/2-Watt (part # 71252 UL listed) for Notification Appliance Circuits
ALARM, TROUBLE, AND SUPERVISORY RELAYS - TB3
ALARM, TROUBLE, AND SUPERVISORY RELAYS - TB3
ALARM, TROUBLE, AND SUPERVISORY RELAYS - TB3
ALARM, TROUBLE, AND SUPERVISORY RELAYS - TB3
ALARM, TROUBLE, AND SUPERVISORY RELAYS - TB3
Contact rating: 2.0 amps @ 30 VDC (resistive), 0.5 amps @ 30 VAC (resistive)
Alarm and Trouble: Form-C
Refer to Figure 2.2 for information on power-limited wiring for relay circuits.
FOUR-WIRE SMOKE DETECTOR POWER (24VDC
FOUR-WIRE SMOKE DETECTOR POWER (24VDC nominal
FOUR-WIRE SMOKE DETECTOR POWER (24VDC
FOUR-WIRE SMOKE DETECTOR POWER (24VDC
FOUR-WIRE SMOKE DETECTOR POWER (24VDC
Max. ripple voltage: 10 mV
Up to 300 mA is available for powering 4-wire smoke detectors
Power-limited circuit
NONRESETTABLE REGULATED 24V POWER (24VDC nominal
NONRESETTABLE REGULATED 24V POWER (24VDC
NONRESETTABLE REGULATED 24V POWER (24VDC
NONRESETTABLE REGULATED 24V POWER (24VDC
NONRESETTABLE REGULATED 24V POWER (24VDC
Max. ripple voltage: 10 mV
Total DC current available from this output is up to 300 mA
Power-limited circuit
NON-REGULATED SPECIAL PURPOSE 24V POWER—TB4 TERMINALS 1 (+) & 2 (-)
NON-REGULATED SPECIAL PURPOSE 24V POWER—TB4 TERMINALS 1 (+) & 2 (-)
NON-REGULATED SPECIAL PURPOSE 24V POWER—TB4 TERMINALS 1 (+) & 2 (-)
NON-REGULATED SPECIAL PURPOSE 24V POWER—TB4 TERMINALS 1 (+) & 2 (-)
NON-REGULATED SPECIAL PURPOSE 24V POWER—TB4 TERMINALS 1 (+) & 2 (-)
Operating voltage range: 18V to 30V
Total DC current available for powering external devices is 2.5 amps
This power is not recommended for AFM, LDM or LCD-40 annunciators
Power-limited circuit
NOTES:
NOTES:
NOTES:
NOTES:
NOTES:
1. For power supply calculations, refer to Appendix A.
2. Total current for special purpose power, nonresettable power, four-wire smoke power, and two
Notification Appliance Circuits must not exceed 6.0 amperes . Total external system current in
excess of 3.6 amperes requires XRM-24E Transformer and 12AH or 17AH batteries, not 7.0 AH.
3. Total current for resettable 4-wire smoke power and non-resettable power must not exceed 600mA.
8
Technical Manuals Online! - http://www.tech-man.com
Normal Flat Charge—27.6V @ .8 amp.
17 AH.
1) Up to 7 AH batteries can be housed in the MS-9200 enclosure.
2) 12 to 17 AH batteries require the Fire•Lite BB-17F or similar UL
listed battery cabinet.
3) 20 to 55 AH batteries require the Fire•Lite R45-24E charger for
housing and charging the batteries.
Supervisory: Form-A
Max. standby current: 50 mA
RMS
Max. standby current: 150 mA
RMS
Document # 50428
firealarmresources.com
2
.
nominal
nominal
nominal) - TB4 TERMINALS 5 (+) & 6 (-)
) - TB4 TERMINALS 5 (+) & 6 (-)
) - TB4 TERMINALS 5 (+) & 6 (-)
) - TB4 TERMINALS 5 (+) & 6 (-)
nominal
) - TB4 TERMINALS 5 (+) & 6 (-)
1, 2, 3
.
nominal
nominal
nominal)—TB4 TERMINALS 3 (+) & 4 (-)
)—TB4 TERMINALS 3 (+) & 4 (-)
)—TB4 TERMINALS 3 (+) & 4 (-)
)—TB4 TERMINALS 3 (+) & 4 (-)
nominal
)—TB4 TERMINALS 3 (+) & 4 (-)
1, 2, 3
2
Rev. B1
7/28/97
P/N 50428:B1