2.6
UL Power-limited
Wiring Requirements
Figure 2-8: Typical Wiring Diagram for UL Power-limited Requirements
22
Technical Manuals Online! - http://www.tech-man.com
Power-limited and nonpower-limited circuit wiring must remain separated in
the cabinet. All power-limited circuit wiring must remain at least 0.25" away
from any nonpower-limited circuit wiring. Furthermore, all power-limited
circuit wiring and nonpower-limited circuit wiring must enter and exit the
cabinet through different knockouts and/or conduits. A typical wiring diagram
for the MS-5024 is shown below.
Power-limited Circuits
AC Power
Earth
Ground
50066 Rev D
5/2/97 P/N 50066:D
firealarmresources.com
Nonpower-limited Circuits
Power-limited Circuits
Power-limited
Circuit