7.9.7 EMS

Path 1: Tap the shortcut icon (
Path 2:
MEASUREMENT
To activate the EMS function of the UPS, you have to connect the optional EMS 1000
(EnviroProbe) device(s) with the UPS; the EMS information of each device (ID #) will be
displayed on the EMS
for the descriptions of each item shown on the EMS screen.
NOTE:
1. The items shown on the EMS screen is related to the settings in the (
EMS Setting; the settings can be adjusted according to your needs.
2. For installation of the optional EMS 1000 (EnviroProbe), please refer to
(EnviroProbe).
No.
Item
ID
1
EMS
attached in the package of the optional EMS 1000
UPS-1.1
MEASUREMENT
SETUP
EMS
EMS
ID
Title
Temperature
0
EMS0
1
EMS1
3
EMS3
6
EMS6
1
Color
(Status)
Green (Normal)
Yellow (Warning)
Red (Alarm)
) on the Main Screen.
MAINTENANCE
LOG IN
Administrator
Humidity
DI1
°C
%
25.4
52
Security 1
°C
%
Security 1
25.8
51
°C
%
Security 1
25.9
51
°C
%
S1
2
3
1. ID # represents each EMS 1000 (EnviroProbe)
device which is connected and set as 'Enable'.
2. Shows the integrated status of each EMS
1000 (EnviroProbe) device. The integrated
status is determined by the most severe status
among Temperature (°C), Humidity (%) and

DI1 ~ DI4.

7-27
7
LCD Display & Settings
and the
10:15
2
May 25,2018
WARNING
On-Line
Normal
Warning
Alarm
Off
DI2
DI3
DI4
2
qqqqq3
qqpo4
2
qqqqq3
qqpo4
2
qqqqq3
qqpo4
L2
F3
S4
4
Descriptions
SETUP