Delta Modulon DPH Series User Manual page 169

Three phase 100-300 kva
Hide thumbs Also See for Modulon DPH Series:
Table of Contents

Advertisement

5
Go to SETUP
UPS-1.1
MEASUREMENT
MODE SETTING
On-Line
6
Switch OFF the Input Breaker (Q1), Bypass Breaker (Q2) and Output Breaker (Q4).
After that, the UPS will run in Standby mode.
7
8
About 3 minutes later, the UPS will shut down, and the LCD and the tri-color LED
9
Switch OFF every external battery cabinet's breaker (Q5).
Mode Setting
On-Line.
SETUP
MAINTENANCE
Mode Setting
Select to change system mode
Green
ECO
6-45
LOG IN
EVENT LOG
Administrator
Energy
Frequency
Recycle
Conversion
6
UPS Operation
10:15
May 25,2018
Bypass

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the Modulon DPH Series and is the answer not in the manual?

This manual is also suitable for:

Dph-300k

Table of Contents