Three phase 100-300 kva
Hide thumbs Also See for Modulon DPH Series:
Table of Contents

Advertisement

Capacity
Suggested
PE Cable
Size
Maximum Cable
Lug Width
Screw Size/ Cable
Lug Inner Diameter
Tightening Torque
Terminal Type*
NOTE:
*
terminals provided by other manufacturers.
Dual Input (Single Unit)
When there are two AC power sources, single unit wiring procedures are as follows.
Modulon DPH Series
100kVA/
100kW
16 mm
× 1 PC
Output
(4 AWG
× 1 PC)
25 mm
× 1 PC
Battery
(2 AWG
× 1 PC)
48 mm
(1.89")
TLAPH250-
1
2A12
1
The suggested manufacturer is K.S. TERMINALS INC. You may use equivalent
Load
Load
Load Grounding
Load Grounding
DPH Series 100-300kVA
150kVA/
150kW
2
2
25 mm
× 1 PC
(2 AWG
× 1 PC)
2
2
25 mm
× 1 PC
(2 AWG
× 1 PC)
48 mm
(1.89")
M10/ 14 mm (0.55")
M10 = 250 ± 10 kgf-cm (217 ± 8.7 lb-in)
TLAPH250-
TLAPH250-
2A12
External
Distribution Panel
Protective Earthing
5-20
200kVA/
250kVA/
200kW
250kW
2
50 mm
35 mm
× 1 PC
× 1 PC
(1/0 AWG
(2 AWG
× 1 PC)
× 1 PC)
2
50 mm
50 mm
× 1 PC
× 1 PC
(1/0 AWG
(1/0 AWG
× 1 PC)
× 1 PC)
48 mm
48 mm
(1.89")
(1.89")
TLAPH250-
2A12
2A12
External
Battery
UPS
Cabinet
UPS Grounding
External Battery Cabinet
Grounding
300kVA/
300kW
2
2
67 mm
× 1 PC
(2/0 AWG
× 1 PC)
2
2
67 mm
× 1 PC
(2/0 AWG
× 1 PC)
48 mm
(1.89")
TLAPH250-
2A12