Ambient Conditions
8.6.1

System with flexible supply unit

Waste heat of the complete
system including the argon laser
Waste heat of the argon laser
For cooling, the argon laser must be connected to the provided argon laser fan. The
following space is required:
Standard fan
Noise-reduced laser fan
In addition, it is possible to connect the argon laser exhaust to an in-house exhaust system:
Hose length
Diameter of adapter piece
Air flow rate
The remaining waste heat (1,9 kW) must be extracted; otherwise the room temperature will
rise.
8.6.2

System with compact supply unit

Waste heat of the complete
system with compact supply unit
8.6.3

External Lasers

38
4,0 kW
1.6 kW
about 30 x 30 cm (1' x 1')
50 x 60 cm (1'8" x 2')
400 cm (13'1"), provided by default
15 cm (6")
400 m³/h (14,126 ft³/h)
2.0 kW
Observe the user manuals for external lasers
Please refer to the information from the documents provided by the laser
manufacturer for the external lasers. Pay particular attention to the laser
manufacturer's notes!