Power Supply - Endress+Hauser PROline Prosonic Flow 93 FOUNDATION Fieldbus Operating Instructions Manual

Ultrasonic flow measuring system
Hide thumbs Also See for PROline Prosonic Flow 93 FOUNDATION Fieldbus:
Table of Contents

Advertisement

10 Technical data
Electrical connection
Supply voltage
Potential equalisation
Cable entry
Cable specifications
Power consumption
Power supply failure
110
10.1.5

Power supply

see Page 37 ff.
85...260 V AC, 45...65 Hz
20...55 V AC, 45...65 Hz
16...62 V DC
No measures necessary.
Power supply and signal cables (inputs/outputs):
• Cable entry M20 x 1.5
or
• Cable gland for cables with dia. 6...12 mm
• Threaded adapter 1/2" NPT, G 1/2"
Sensor cable connection (see Fig. 41 on Page 40):
A special cable gland allows you to insert both sensor cables (per channel) into the
connection compartment simultaneously.
• Cable gland M20 x 1.5 for 2 x dia. 4 mm
or
• Threaded adapter 1/2" NPT, G 1/2"
See Page 40
AC: < 18 VA (incl. measuring sensors)
DC: < 10 W (incl. measuring sensors)
Switch-on current:
• Max. 13.5 A (< 50 ms) at 24 V DC
• Max. 3 A (< 5 ms) at 260 V AC
Lasting min. 1 cycle frequency:
• EEPROM or T-DAT save measuring system data if power supply fails.
• T-DAT saves the configuration/setting values of the transmitter.
If necessary, the T-DAT data can be loaded into the EEPROM (manual save function).
PROline Prosonic Flow 93 FOUNDATION Fieldbus