Endress+Hauser PROline Prosonic Flow 93 FOUNDATION Fieldbus Operating Instructions Manual page 71

Ultrasonic flow measuring system
Hide thumbs Also See for PROline Prosonic Flow 93 FOUNDATION Fieldbus:
Table of Contents

Advertisement

PROline Prosonic Flow 93 FOUNDATION Fieldbus
Endress+Hauser
22. System configuration/connection of function blocks (see Fig. 55):
A concluding "overall system configuration" is essential so that the Analog Input
function block can be set to the AUTO operating mode and so that the field device
is integrated into the system application.
To do this, configuration software such as the NI-FBUS Configurator from National
Instruments is used to connect the function blocks to the desired control strategy –
generally graphically – and then the sequence of the individual process control
functions is specified.
Fig. 55:
Connecting function blocks using the NI-FBUS Configurator
23. After specifying the active LAS (Link Active Schedule), download all the data and
parameters into the field device.
24. Set the operating mode of the Analog Input function block to AUTO
(MODE_BLK parameter group, "Target" parameter = AUTO).
However, this is only possible if two conditions are met:
– The function blocks are correctly connected with each other.
– The Resource Block is also in the AUTO operating mode
(MODE_BLK parameter group, "Actual" parameter = "AUTO").
6 Commissioning
71