PROline Prosonic Flow 93 FOUNDATION Fieldbus
Endress+Hauser
5.
Identify the field device using the DEVICE_ID that you noted down and assign the
desired tag name (PD_TAG) to the fieldbus device in question.
Factory setting: E+H_PROSONIC_FLOW_93_xxxxxxxxxxx
Fig. 54:
Screen display in the configuration programme "NI-FBUS Configurator" (National Instruments) after
connecting
Configuring the "Resource Block" (base index 258)
6.
Open the Resource Block.
7.
On delivery, write protection is disabled so that you can access the write
parameters via the FOUNDATION Fieldbus.
Check this status via the WRITE_LOCK parameter:
– Write protection enabled = LOCKED
– Write protection disabled = NOT LOCKED
Disable the write protection, if necessary → Page 53.
8.
Enter the desired block name (optional).
Factory setting: RESOURCE_ xxxxxxxxxxx
9.
Set the operating mode in the MODE_BLK parameter group (TARGET parameter )
to AUTO.
6 Commissioning
67