Installing the measuring sensors Prosonic Flow P

2 or 4 traverses version
1.
Fix a tensioning band for small or large nominal diameters as described on
Page 17.
2.
Fix the sensor holder to the pipe using the threaded stud.
Tighten the locking nut using a spanner (AF 13).
3.
Fasten the mounting rail bracket to the sensor holder using a Philips screwdriver.
Fig. 11:
Installation steps 1 to 3, measuring sensors Prosonic Flow P, 2 or 4 traverses version
Intermediate step:
Install the second sensor holder as per steps 1 to 3.
Make sure that the tensioning band is not fastened.
You must still be able to move the sensor holder along the pipe.
4.
The spacing between the distance holes (sensor distance) is determined
by means of the "Sensor" Quick Setup (for devices with a local display).
Run the Quick Setup as explained on Page 72.
The sensor distance is displayed in the "Position sensor" function (6884), (i.e. a
letter between A...K for sensor 1 and a number between 10...76 for sensor 2).
Use the mounting rail as appropriate (for DN 50...200 or for DN 200...600) and
tighten the relevant screws.
Now fasten the second tensioning band.
!
Note!
– The transmitter must have a local display and be installed and connected to the
power supply before you can run the "Sensor" Quick Setup.
– In the case of transmitters without a local display, the value can be determined as
explained on Page 63.