Minimum Sub-Menu; Maximum Sub-Menu - Eaton Cutler-Hammer FP-5000 Instructions Manual

Protective relay
Hide thumbs Also See for Cutler-Hammer FP-5000:
Table of Contents

Advertisement

IL17569
4.6.1.5 Selecting the "Minimum" Sub-menu
This menu allows the user to view the following system parameters.
(See Display 4.8 Minimum Sub-menu.)
• Minimum currents (IA, IB, IC, IX, IR)
• Minimum L-L Voltages (VAB, VBC, VCA)
• Minimum L-N Voltages (VA, VB, VC)
• Minimum Power (Watt, Var, VA)
• Minimum Frequency
• Minimum Power Factor (Apparent, Displacement)
Display 4.8 Minimum Sub-menu
Min <Variable>
(Variable)
Magnitude
Date
mm/dd/yy
Time
hh:mm:ss
Min Rst Date & Time
Date
mm/dd/yy
Time
hh:mm:ss
Table 4.2 Minimum Sub-menu
Where <Variable> (Variable) =
<IA Current>
<IB Current>
<IC Current>
<IX Current>
<IR Current>
<VAB Voltage>
<VBC Voltage>
<VCA Voltage>
<VA Voltage>
<VB Voltage>
<VC Voltage>
<System Watts>
<System Vars>
<System VA>
<Frequency>
<Apparent PF>
<Displacement PF>
The Date and Time Stamp is also recorded on the same page with
the minimum value display for each parameter occurance.
The minimum values for each of the above parameters is compared
to the last minimum value for that parameter every 32 cycles. If the
new value is less than the last minimum, the value is updated.
Power Factor Minimum is the most leading power factor value
measured.
Effective June, 2001
4.6.1.6 Selecting the "Maximum" Sub-menu
This menu allows the user to view the following system
parameters. (See Display 4.9 Maximum Sub-menu.)
• Maximum currents (IA, IB, IC, IX, IR)
• Maximum L-L Voltages (VAB, VBC, VCA)
• Maximum L-N Voltages (VA, VB, VC)
• Maximum Power (Watt, Var, VA)
• Maximum Frequency
• Maximum Power Factor (Apparent, Displacement)
Display 4.9 Maximum Sub-menu
Table 4.3 Maximum Sub-menu
Where <Variable> (Variable) =
(IA)
(IB)
(IC)
(IX)
(IR)
(VAB)
(VBC)
(VCA)
(VA)
(VB)
(VC)
(M Watts)
(M VAR)
(MVA)
(Freq)
(Apt PF)
(Disp PF)
The Date and Time Stamp is also recorded on the same page with
the minimum value display for each parameter occurance.
The maximum values for each of the above parameters is com-
pared to the last maximum value for that parameter every 32 cycles.
If the new value is greater than the last maximum, the value is
updated. Power Factor Maximum is the most lagging power factor
value measured.
Max <Variable>
(Variable)
Magnitude
Date
mm/dd/yy
Time
hh:mm:ss
Min Rst Date & Time
Date
mm/dd/yy
Time
hh:mm:ss
<IA Current>
<IB Current>
<IC Current>
<IX Current>
<IR Current>
<VAB Voltage>
<VBC Voltage>
<VCA Voltage>
<VA Voltage>
<VB Voltage>
<VC Voltage>
<System Watts>
<System Vars>
<System VA>
<Frequency>
<Apparent PF>
<Displacement PF>
Page 4-9
(IA)
(IB)
(IC)
(IX)
(IR)
(VAB)
(VBC)
(VCA)
(VA)
(VB)
(VC)
(M Watts)
(M VAR)
(M VA)
(Freq)
(Apt PF)
(DisP PF)