12.1.4 Transient Messages
The following display messages replace the normal display for the indicated time duration or until a pushbutton is pressed. The messages
are in response to transient conditions as described in Table 12.2
Table 12.2 FP-5000 Transient Messages
Condition
Display if current is sensed during fault simulation
Open breaker pushbutton with breaker open
Close breaker pushbutton with breaker closed
Update clock
Display if "Set" pushbutton is pressed
while a remote setting download is in progress
Displayed when a download of settings occur
Settings are saved and being processed
Effective June, 2001
Status Flag
Protection
Calibration
Disabled
Enabled
Disabled
Enabled
Enabled
Enabled
Disabled
Description
The calibration
constants have been
corrupted
A recoverable
corruption of the
setpoints has
occurred
A test simulation has
begun
A recoverable
corruption of the
calibration setpoints
has occurred
The EEPROM has
been written to a
large number of
times and is in danger
of wearing out
Because the
EEPROM has been
written to a large
number of times no
more writes are
permitted
The Disarmed
function has been
activated
Display Message Text
"Fault Test Aborted"
"Error: Breaker Open"
"Error: Breaker Closed"
"Clock Update Confirmed"
"Remote Setting Change
in Progress"
Remote Download Settings ...
"Saving Settings To EEPROM
in Progress"
Recommended Action
The circuit is not protected, replace
FP-5000 immediately.
Check the settings in the FP-5000,
making corrections if needed. If
this warning repeats then replace
the FP-5000.
To stop the test, press the Test
button, select Fault Simulation,
and select Stop Simulation.
Check the accuracy of the voltage
current input measurement. If this
warning repeats then replace the
FP-5000.
Call the factory, for troubleshooting
help.
Call the factory, for troubleshooting
help.
The Disarmed feature can be
turned off by pressing the "Test"
pushbutton selecting Arm/Disarm
Trip, and selecting Arm Trip.
Duration
5 seconds
5 seconds
5 seconds
5 seconds
5 seconds
1 second
1 second
Page 12-3