Page 5-8
Table 5.2 Unbalance Setting (continued)
Display Setting
Description
46-1 Current
Current Unbalance Settings
Unbal
Threshold:
Select magnitude
of unbalance required
(either I1 or I2)
% (I2/I1):
Percent negative sequence (I2)
divided by positive sequence (I1)
Delay (c):
Select delay time in cycles
Table 5.2 Main V Protection: Selects undervoltage (27M-1) and overvoltage (59M-1) device settings
27M-1
Main VT Undervoltage Settings
Undervoltage
Threshold V:
Select magnitude
of undervoltage required
Delay (c):
Select delay time in cycles
59M-1
Main VT Overvoltage Settings
Overvoltage
Threshold V:
Select magnitude
of overvoltage required
Delay (c):
Select delay time in cycles
Table 5.2 Aux V Protection: Selects undervoltage (27A-1) and overvoltage (59A-1) device settings
27A-1
Auxiliary VT Undervoltage Settings
Undervoltage
Threshold V:
Select magnitude
of undervoltage required
Delay (c):
Select delay time in cycles
59A-1
Auxiliary VT Overvoltage Settings
Overvoltage
Threshold V:
Select magnitude
of overvoltage required
Delay (c):
Select delay time in cycles
Setpoint Range/
Value Selection
0.1 to 20.0, disable
(0.01 pu increments)
4 to 40 percent
(1% increments)
0 to 9999 cycles
(1 cycle increments)
10 to 150 volts, disable
(1 volt increments)
0 to 9999 cycles
(1 cycle increments)
10 to 150 volts, disable
(1 volt increments)
0 to 9999 cycles
(1 cycle increments)
10 to 250 volts, disable
(1 volt increments)
0 to 9999 cycles
(1 cycle increments)
10 to 250 volts, disable
(1 volt increments)
0 to 9999 cycles
(1 cycle increments)
IL17569
Default
Selected
Refer to
Setting
Value
Sec. #
5.5.2.4
8.3.5
Disable
20
600
5.5.2.5
8.6.2
Disable
1200
5.5.2.5
8.6.2
Disable
1200
5.5.2.5
8.6.2
Disable
1200
5.5.2.5
8.6.2
Disable
1200
Effective June, 2001