Eaton Cutler-Hammer FP-5000 Instructions Manual page 21

Protective relay
Hide thumbs Also See for Cutler-Hammer FP-5000:
Table of Contents

Advertisement

Page 3-2
Relay Output Contacts Rating:
Momentary
Continuous
IPONI Communications:
Baud Rate
Max. distance
Protocol
Media
Signal lines
Shield
DC input impedance
AC input impedance @ 100 kHz
Accessory Bus:
Baud Rate
Max. distance
Protocol
Media
Signal lines
Shield
DC input impedance
AC Input impedance @ 100 kHz
Zone Interlock:
Zone Out
Zone In
Zone Common
Zone Shield
Cable
RS-232:
Baud Rate
Connector
Protocol
Cable
Both Form A & C
Make 30A AC/DC for 0.25 s.
Break 0.5A @ 125V DC (resistive)
Break 5A @ 120V AC
5A @ 120/240V AC
5A @ 30V DC
TB3 J1
9600 Fixed
10,000 feet
INCOM Slave
Shielded Twisted pair - CH IMPCABLE; BELDEN 9463, 3072F
J1-1, J1-2 polarity not needed
J1-3 Filter referenced to chassis
~2 ohms
> 30k/100 ohms unterminated/terminated - Switch
TB3 J2, - FUTURE INTERFACE
9600 Fixed
10,000 feet
INCOM
Shielded Twisted pair - CH IMPCABLE: Belden 9463, 3072F
J2-1, 2-2 polarity not needed
J2-3 Filter referenced to chassis
~2 ohms
> 100 ohms (permanent termination resistor)
TB3 J3
J3-1 Open collector output ~ 4.5V to common
J3-4, Approximately 300K ohms input impedance
J3-2, 3-5 internally connected
J3-3 referenced direct to chassis – NOT REQUIRED
14-18 AWG Twisted Pair <250' between 1
Front temporary programming monitor port
PowerPort Connection
38.4 kB, 19.2 kB, 9.6 kB
Standard 9-Pin D Subminiature, DCE Connection P2, 3, 5
INCOM ASCII Slave
Shielded & restricted to < 3 meters in length
IL17569
st
and last unit
Effective June, 2001

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents