Logic Input Settings - Eaton Cutler-Hammer FP-5000 Instructions Manual

Protective relay
Hide thumbs Also See for Cutler-Hammer FP-5000:
Table of Contents

Advertisement

IL17569

5.4 Logic Input Settings

Table 5.10 Logic Input Setting Options
Logic Input (IN1, IN2, IN3, & IN4) Programming Option Settings: Logic input settings for the 8 logic categories
Input Category
"Available Setting Options"
Unused
Unused
Pickup
PH OC, G OC, IOC, TOC, OC, All Alm, Volt, Freq, AllProt, 50X-1, 50X-2,
50X-3, 50R-1, 50R-2, 50R-3, 50P-1, 50P-2, 50P-3, 51P, 51X, 51R, 59A-1,
59A-2, 27A-1, 27A-2, 59M-1, 59M-2, 27M-1, 27M-2, 46-1, 46-2, 47-1,
47-2, 81U-1, 81U-2, 81O-1, 81O-2, BF, 55A PF,
Trip
PH OC, G OC, IOC, TOC, OC, All Alm, Volt, Freq, AllProt, 50X-1, 50X-2,
50X-3, 50R-1, 50R-2, 50R-3, 50P-1, 50P-2, 50P-3, 51P, 51X, 51R, 59A-1,
59A-2, 27A-1, 27A-2, 59M-1, 59M-2, 27M-1, 27M-2, 46-1, 46-2, 47-1,
47-2, 81U-1, 81U-2, 81O-1, 81O-2, BF, 55A PF,
Logic
LG1, LG2, LG3, L54, LG5, LG6, TG1, TG2, TG3, TG4,
TG5, TG6, Q1, or Q2
Inputs
Cin1, Cin2, Cin3, Cin4, Cin5, Cin6, Cin7, Cin8, or ZI In
SysAlm
Watt, VAR, VA, WattDmd, VARDmd, VADmd, CurDmd, V THD, I THD,
BkrOps, Sum I, or AllAlm
Breaker
OpenBkr, CloseBkr, Open, Closed, BkrFail, SlowBkr, StateAlm,
Mntr1Alm, Mntr2Alm or All Alm
Comm
Comm1, Comm2, Comm3 or Comm4
Effective June, 2001
Page 5-31
Setpoint Range/
Value Selection
Direct or Negated
Direct or Negated
Direct or Negated
Direct or Negated
Direct or Negated
Direct or Negated
Direct or Negated
Direct or Negated