Event General Cause Table; Event Pickup, Or Dropout Cause Table - Eaton Cutler-Hammer FP-5000 Instructions Manual

Protective relay
Hide thumbs Also See for Cutler-Hammer FP-5000:
Table of Contents

Advertisement

IL17569
Table 12.4 Event General Cause Table
Cause
Cause Description
PwrOn
The FP-5000 is powered on
PwrOff
The FP-5000 is powered off
FltPwrOp
Transition to Fault Powered Operation
SetChange
The program settings are changed and saved
PRSetGrpCh
The protection active setting group is changed
SetRTC
The real time clock is set to a new date/time
Trig Wfm Capt
The trigger for a waveform capture is activated
Rst Trip/Alm
A reset of the trip or alarm is performed
Reset Energy
The energy values are reset
RstCurPKDmd
The current peak demand values are reset
RstPwrPKDmd
The power peak demand values are reset
RstMinMax
The min and max values are reset
RstHistLog
The history log has been reset
ClrDataLogger
The data logger saved data is cleared
Default Set
The setpoints are returned to the default settings
Every pickup and dropout of an enabled protection function can be logged in the Event log. Each class of pickups must be programmed to be
logged (see Section 5). Observing pickups in the Event log can show if a current or voltage transient is causing a pickup. Most values given
with each log can be accessed by selecting the line immediately below the Cause and pressing Enter. The information given is a series of
status flags that show the state of that status at the time of the event. Table 12.5 shows all the possible event causes that are a pickup or a
dropout of a protective function.

12.5 Event Pickup, or Dropout Cause Table

Cause
Cause Description
50P IOC
Phase Instantaneous Over Current
is picked up or dropped out
50X IOC
IX (ground) Instantaneous Over
Current is picked up or dropped out
50R IOC
IR Residual Instantaneous Over Current
is picked up or dropped out
51P TOC
Phase Time Over Current is picked up
or dropped out
51X TOC
IX (ground) Time Over Current has
picked up or dropped out
51R TOC
IR Residual Time Over Current has
picked up or dropped out
59M OV
Main Phase Over Voltage has picked
up or dropped out
27M UV
Main Phase Under Voltage has picked
up or dropped out
Effective June, 2001
Value Given
No value associated with this cause
No value associated with this cause
No value associated with this cause
The Setpoint Sequence number
The new active setting group number
(#1 - #4)
No value associated with this cause
The event that has caused the trigger –
dV/dI, Logic, PB, Comm
No value associated with this cause
No value associated with this cause
No value associated with this cause
No value associated with this cause
No value associated with this cause
No value associated with this cause
No value associated with this cause
The Setpoint Sequence number
Value Given
IOC Pickup Status – contains status flags that describe
the state of all possible IOC pickups
IOC Pickup Status – contains status flags
that describe the state of all possible IOC pickups
IOC Pickup Status – contains status flags that describe
the state of all possible IOC pickups
TOC Pickup Status – contains the status flags that
describe the state of all possible TOC pickups
TOC Pickup Status – contains the status flags that describe
the state of all possible TOC pickups
TOC Pickup Status – contains the status flags that describe
the state of all possible TOC pickups
Voltage Pickup Status – contains the status flags that
describe all under and over voltage pickups
Voltage Pickup Status – contains the status flags that
describe all under and over voltage pickups
Page 12-5