5.3 FP-5000 Setting Table

NOTE:
All voltage settings are in secondary units. All current settings are in per unit. All System settings are in primary units. Time delay
setting is in cycles (c), seconds (s), or minutes (m).
Program Date:
FP-5000 Relay ID:
Work Order #:
Table 5.1 System Config
Display Setting
Description
Frequency:
Nominal system
operating frequency
Phase Seq:
Nominal system phase
sequence or rotation
Ct Connect:
Ct connect determines how
residual current IR is calculated
3-wire: 4th Ct is independent
4Ct In: 4-wire system with
4th Ct on neutral conductor
4Ct Ig: 4-wire system with
4th Ct on ground conductor
PH Ct Ratio:
Ct ratio of the phase
current Cts
IX Ct Ratio:
Ct ratio of the fourth Ct
VT Connect:
Voltage transformer
connection
Main VTR:
Main voltage
transformer ratio:1
Aux VTR:
Auxiliary voltage
transformer ratio:1
Prim Units:
Selection of primary or
secondary units of displayed
values
I/O Config:
Default input/output
configuration or customized
input/output
Prog Logic:
Default or custom
Programmable logic settings
Remote Set:
Enables or disables remote
download setpoints capability
from rear communication port
Effective June, 2001
Control Schematic:
Breaker ID:
Line Protected:
Setpoint Range/
Value Selection
50 Hz or 60 Hz
ABC or ACB
3-wire, 4Ct In, 4Ct Ig
I
to 6000
nom
(Increments of I
)
nom
I
to 6000
nom
(Increments of I
)
nom
Wye or Delta
1 to 8000
(Increments of 1)
1 to 8000
(Increments of 1)
Yes, No
Default or Custom 1
Default or Custom 1
Enable or disable
Default
Selected
Setting
Value
60
ABC
3-wire
500:I
3
nom
500:I
3
nom
Wye
100
100
No
Default
Default
Enable
Page 5-3
Refer to
Sec. #
5.5.1
5.5.1
5.5.1
8.2
5.5.1
5.5.1
5.5.1
6.3.2
5.5.1
5.5.1
5.5.1
5.5.1
5.5.1
5.5.1