Standards Compliance - Eaton Cutler-Hammer FP-5000 Instructions Manual

Protective relay
Hide thumbs Also See for Cutler-Hammer FP-5000:
Table of Contents

Advertisement

IL17569
Dimensions
Behind Panel:
Height
Width
Depth
In Front of Panel:
Height
Width
Depth
Weight:
Drawout
Enclosure
Adapter Panel
Shipping
FS (Full Scale) = 3 • CT Rating • Nominal L-N Voltage.
1
Minimum absolute tolerance of measured current is 0.5% of CT Rating.
2
Minimum absolute tolerance of residual current is 3% of CT Rating.
3
Minimum absolute tolerance of measured voltage is 0.5% of Nominal Voltage.
4
Note shield & VG exception details in Section 7 "Startup."
5

3.2 Standards Compliance

The FP-5000 complies with the following standards except
where noted:
• ANSI/IEEE C37.90-1989, Standard for Relay Systems associated
with electric power apparatus.
• UL/CUL-1053 Recognized – Ground Fault Sensing and Relaying
Equipment File E154862:
– FP5000-00 5A CT model only
– FP5100-00 1A CT pending
• EMC Requirements:
– ANSI C37.90.1 (1989) Surge withstand all ports
– ANSI C37.90.2 (1995) RF withstand
Emissions (EN-50081-2):
• EN 50011
CISPR-11, Class A
• CFR 47 FCC Part 15 Subpart b Class A
Effective June, 2001
6.7 in. (17.0 cm)
5.3 in. (13.5 cm)
6.9 in. (17.75 cm)
11.34 in. (28.9 cm)
7.72 in. (19.7 cm)
0.80 in. (2.1 cm)
5.8 lbs (2.6 Kg)
5.0 lbs (2.3 Kg)
1.3 lbs (.6 Kg)
16.5 lbs (7.5 Kg)
Immunity (EN-61000-6-2):
• ENV 61000-4-2
ESD Immunity
• ENV 61000-4-3
RF Radiated Immunity
• ENV 61000-4-4
EFT Immunity
• EN 61000-4-5
Surge Withstand
• EN 61000-4-6
RF Conducted Immunity
• EN 61000-4-8
Power Frequency Magnetic Field Immunity
• EN 61000-4-11
Voltage Dips, Short Interruption and Voltage
Variation Immunity
See Appendix Section 13.5 for compliance levels
and related information.
Page 3-5