Pushbuttons; Transient Display Messages - Eaton Cutler-Hammer FP-5000 Instructions Manual

Protective relay
Hide thumbs Also See for Cutler-Hammer FP-5000:
Table of Contents

Advertisement

IL17569
Table 4.1 Transient Display Messages
"Display Message"
Functions Programmed to
default. They can be
viewed only.
See System Config.
Fault Test is Off!
Zone Interlock Output is On
Zone Interlock Output Is Off

4.3 Pushbuttons

The front operations panel supports 15 membrane switch
pushbuttons. Pressing any of the pushbuttons will initiate many
of the FP-5000 functions and actions. This section gives a complete
description of each pushbutton and its functions. The pushbuttons
can be grouped logically into the 6 display modes, reset and
breaker control.
1. Reset
2. Monitor
3. View Setting
4. Log
The center section consists of display navigation buttons:
1. Previous
2. Up/Down (single arrow)
3. Up/Down (double arrow)
4. Enter
"Reset" Pushbutton:
The "Reset"pushbutton performs many "Reset"
functions, one of which resets the display to
show the default rms current and voltage display
screen from any display menu, when the relay
is in normal monitoring mode.
The FP-5000 has a "Reset" menu, which is
accessed by pressing the "Reset" pushbutton
when the unit is in normal monitoring mode. This
menu allows the user to reset all of the relay
functions: trips, alarms, peak current and power
demands, min/max values, history log param-
eters, relays, and the data logger. There is no
password protection for the reset functions.
(See Display 4.2)
Effective June, 2001
5. Status/Control
6. Set (Settings)
7. Test
8. Close Open Breaker
Display Mode
Flashing a few seconds in
the setting-edit mode
5 seconds in Test mode
5 seconds in Test mode
5 seconds in Test mode
Display 4.2 Reset
Reset Main
Trip
Alarm
Bkr Lockout
Slow Bkr ALM
Relay
Peak Demand Values
Min/Max Values
History Log
Datalog
Energy
Display
Diag Warnings
By selecting a Reset sub-menu function listed above by using the
Up/Down arrow and "Enter" pushbutton, the user can reset that
function simply by pushing the "Enter" pushbutton again. The example
below shows the "Trip Flag" sub-menu reset display screen.
Reset Trip
Press
ENTER To Confirm
PREVIOUS To Cancel
Cause
When entering PLC, Cin and Cout
in the setting-edit mode if they
are disabled
When stopping fault simulation if
the test was complete
When turning the Zone Interlock
output on if it is on
When turning the Zone Interlock
output off if it is off
Page 4-3